5.5 GROUPED ELEMENTS
PATH: SETTINGS
GROUPED ELEMENTS
LOSS OF
EXCITATION
5
The operating characteristic is shaped out of two offset mho circles shifted down along the imaginary axis as shown below.
5-144
SETTING GROUP 1(6)

LOSS OF EXCITATION

FUNCTION: Disabled
LOSS OF EXCITATION
MESSAGE
SOURCE: SRC 1
LOSS OF EXCITATION
MESSAGE
CENTER 1: 10.00 ohm
LOSS OF EXCITATION
MESSAGE
RADIUS 1: 8.00 ohm
EXCITATION V SUPV 1:
MESSAGE
Enabled
LOSS OF EXCITATION
MESSAGE
PKP DELAY1: 0.050 s
LOSS OF EXCITATION
MESSAGE
CENTER 2: 12.00 ohm
LOSS OF EXCITATION
MESSAGE
RADIUS 2: 10.00 ohm
LOSS OF EXCITATION
MESSAGE
V SUPV 2: Enabled
LOSS OF EXCITATION
MESSAGE
PKP DELAY2: 0.500 s
LOSS OF EXCITATION
MESSAGE
UV SUPV: 0.700 pu
LOSS OF EXCIT BLK:
MESSAGE
Off
LOSS OF EXCITATION
MESSAGE
TARGET: Self-reset
LOSS OF EXCITATION
MESSAGE
EVENTS: Disabled
X
Figure 5–85: LOSS OF EXCITATION OPERATING CHARACTERISTICS
G60 Generator Management Relay
5.5.13 LOSS OF EXCITATION
LOSS OF EXCITATION
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.01
Range: 0.000 to 1.250 pu in steps of 0.001
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
C1
= Center of element 1 = (Zb + X'd) / 2
R1
= Radius of element 1 = Zb / 2
C2
= Center of element 2 = (Xd + X'd) / 2
R2
= Radius of element 2 = Xd / 2
Zb
= Base impedance of the machine
X'd
= Transient reactance of the machine
Xd
= Synchronous reactance of the machine
830711A1.CDR