GE G60 Instruction Manual page 3

Ur series generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

Addendum
g
This Addendum contains information that relates to the G60 Generator Management Relay relay, version 5.2x. This
addendum lists a number of information items that appear in the instruction manual GEK-113321A (revision P2) but are
not included in the current G60 operations.
The following functions/items are not yet available with the current version of the G60 relay:
• Signal Sources SRC 5 and SRC 6
Version 4.0x and higher releases of the G60 relay includes new hardware (CPU and CT/VT modules).
• The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, and 9R.
• The new CT/VT modules are specified with the following order codes: 8F, 8G, 8H, 8J 8L, 8M, 8N, 8R.
The following table maps the relationship between the old CPU and CT/VT modules to the newer versions:
MODULE
CPU
CT/VT
The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R), and the old CT/
VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mismatches, the new
CPU and CT/VT modules have blue labels and a warning sticker stating "Attn.: Ensure CPU and DSP module label
colors are the same!". In the event that there is a mismatch between the CPU and CT/VT module, the relay will not
function and a
DSP ERROR
All other input/output modules are compatible with the new hardware.
ADDENDUM
OLD
NEW
DESCRIPTION
9A
9E
RS485 and RS485 (Modbus RTU, DNP)
9C
9G
RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP)
9D
9H
RS485 and redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP)
--
9J
RS485 and multi-mode ST 100Base-FX
--
9K
RS485 and multi-mode ST redundant 100Base-FX
--
9L
RS485 and single mode SC 100Base-FX
--
9M
RS485 and single mode SC redundant 100Base-FX
--
9N
RS485 and 10/100Base-T
--
9P
RS485 and single mode ST 100Base-FX
--
9R
RS485 and single mode ST redundant 100Base-FX
8A
8F
Standard 4CT/4VT
8B
8G
Sensitive Ground 4CT/4VT
8C
8H
Standard 8CT
8D
8J
Sensitive Ground 8CT/8VT
--
8L
Standard 4CT/4VT with enhanced diagnostics
--
8M
Sensitive Ground 4CT/4VT with enhanced diagnostics
--
8N
Standard 8CT with enhanced diagnostics
--
8R
Sensitive Ground 8CT/8VT with enhanced diagnostics
or
error will be displayed.
HARDWARE MISMATCH