Overfrequency - GE G60 Instruction Manual

Ur series generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5 SETTINGS
PATH: SETTINGS
CONTROL ELEMENTS

OVERFREQUENCY 1

MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
There are four overfrequency elements, numbered 1 through 4.
A frequency calculation for a given source is made on the input of a voltage or current channel, depending on which is
available. The channels are searched for the signal input in the following order: voltage channel A, auxiliary voltage chan-
nel, current channel A, ground current channel. The first available signal is used for frequency calculation.
The steady-state frequency of a power system is an indicator of the existing balance between the generated power and the
load. Whenever this balance is disrupted through the disconnection of significant load or the isolation of a part of the sys-
tem that has a surplus of generation, the effect will be an increase in frequency. If the control systems of the generators do
not respond fast enough, to quickly ramp the turbine speed back to normal, the overspeed can lead to the turbine trip. The
overfrequency element can be used to control the turbine frequency ramp down at a generating location. This element can
also be used for feeder reclosing as part of the "after load shedding restoration".
The
setting selects the source for the signal to be measured. The
OVERFREQ 1 SOURCE
the level at which the overfrequency element is to pickup.
SETTING
OVERFREQ 1 FUNCTION:
Disabled = 0
Enabled = 1
SETTING
OVERFREQ 1 BLOCK:
Off = 0
SETTING
OVERFREQ 1 SOURCE:
Frequency
GE Multilin
OVERFREQUENCY
OVERFREQ 1 FUNCTION:
Disabled
OVERFREQ 1 BLOCK:
Off
OVERFREQ 1 SOURCE:
SRC 1
OVERFREQ 1 PICKUP:
60.50 Hz
OVERFREQ 1 PICKUP
DELAY:
0.500 s
OVERFREQ 1 RESET
DELAY : 0.500 s
OVERFREQ 1 TARGET:
Self-reset
OVERFREQ 1 EVENTS:
Disabled
SETTING
OVERFREQ 1 PICKUP :
AND
RUN
f
PICKUP
Figure 5–99: OVERFREQUENCY SCHEME LOGIC
G60 Generator Management Relay
5.6 CONTROL ELEMENTS
OVERFREQUENCY 1(4)
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 20.00 to 65.00 Hz in steps of 0.01
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
OVERFREQ 1 PICKUP
SETTING
OVERFREQ 1 PICKUP
DELAY :
FLEXLOGIC OPERANDS
OVERFREQ 1 RESET
OVERFREQ 1 PKP
DELAY :
OVERFREQ 1 DPO
t
PKP
OVERFREQ 1 OP
t
RST
5.6.5 OVERFREQUENCY
setting selects
827832A5.CDR
5-165
5