B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 19 of 47)
ADDR
REGISTER NAME
6661
Accidental Energization Source
6662
Accidental Energization Arming Mode
6663
Accidental Energization OC Pickup
6665
Accidental Energization UV Pickup
6667
Accidental Energization Offline
B
6668
Accidental Energization Block
6669
Accidental Energization Target
666A
Accidental Energization Events
666B
Reserved (5 items)
Loss of Excitation (Read/Write Grouped Setting)
6680
Loss Of Excitation Function
6681
Loss Of Excitation Signal Source
6682
Loss Of Excitation Center 1
6683
Loss Of Excitation Radius 1
6684
Loss Of Excitation UV Supervision Enable 1
6685
Loss Of Excitation Pickup Delay 1
6686
Loss Of Excitation Center 2
6687
Loss Of Excitation Radius 2
6688
Loss Of Excitation UV Supervision Enable 2
6689
Loss Of Excitation Pickup Delay 2
668A
Loss Of Excitation UV Supervision
668B
Loss Of Excitation Block
668C
Loss Of Excitation Target
668D
Loss Of Excitation Events
668E
Reserved (5 items)
Sensitive Directional Power (Read/Write Grouped Setting) (2 modules)
66A0
Sensitive Directional Power 1 Function
66A1
Sensitive Directional Power 1 Signal Source
66A2
Sensitive Directional Power 1 RCA
66A3
Sensitive Directional Power 1 Calibration
66A4
Sensitive Directional Power 1 STG1 SMIN
66A5
Sensitive Directional Power 1 STG1 Delay
66A6
Sensitive Directional Power 1 STG2 SMIN
66A7
Sensitive Directional Power 1 STG2 Delay
66A8
Sensitive Directional Power 1 Block
66A9
Sensitive Directional Power 1 Target
66AA
Sensitive Directional Power 1 Events
66AB
Reserved (5 items)
66B0
...Repeated for Sensitive Directional Power 2
Third Harmonic Neutral Undervoltage (Read/Write Grouped Setting)
6730
Third Harmonic Neutral Undervoltage Function
6731
Third Harmonic Neutral Undervoltage Pickup
6733
Third Harmonic Neutral Undervoltage Delay
6734
Third Harmonic Neutral Undervoltage Max Power
6736
Third Harmonic Neutral Undervoltage Min Power
6738
Third Harmonic Neutral Undervoltage Volt Supervision
6739
Third Harmonic Neutral Undervoltage Block
673A
Third Harmonic Neutral Undervoltage Target
673B
Third Harmonic Neutral Undervoltage Events
673C
Reserved (4 items)
Generator Unbalance (Read/Write Grouped Setting)
6740
Generator Unbalance Function
6741
Generator Unbalance Source
6742
Generator Unbalance Source
B-26
RANGE
0 to 5
0 to 1
0 to 3
0 to 3
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0.1 to 300
0.1 to 300
0 to 1
0 to 65.535
0.1 to 300
0.1 to 300
0 to 1
0 to 65.535
0 to 1.25
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 359
0 to 0.95
-1.2 to 1.2
0 to 600
-1.2 to 1.2
0 to 600
---
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 30
0 to 600
0 to 30
0 to 30
0 to 1.25
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 1.25
G60 Generator Management Relay
UNITS
STEP
FORMAT
---
1
F167
---
1
F193
0 (UV AND OFFLINE)
---
0.001
F003
---
0.001
F003
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
ohm
0.01
F001
ohm
0.01
F001
---
1
F102
s
0.001
F001
ohm
0.01
F001
ohm
0.01
F001
---
1
F102
s
0.001
F001
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
degrees
1
F001
degrees
0.05
F001
pu
0.001
F002
s
0.01
F001
pu
0.001
F002
s
0.01
F001
---
---
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F102
pu
0.0001
F003
s
0.01
F001
pu
0.001
F003
pu
0.001
F003
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
APPENDIX B
DEFAULT
0 (SRC 1)
300
500
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
800
1 (Enabled)
50
1200
1000
1 (Enabled)
500
700
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0
0
100
50
100
2000
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
3000
0
200
200
500
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
800