GE G60 Instruction Manual page 123

Ur series generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5 SETTINGS
h) WEB SERVER HTTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
WEB SERVER
HTTP PROTOCOL
The G60 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft
Internet Explorer or Netscape Navigator. This feature is available only if the G60 has the ethernet option installed. The web
pages are organized as a series of menus that can be accessed starting at the G60 "Main Menu". Web pages are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, Event Records, Fault Reports, etc. The web pages can
be accessed by connecting the UR and a computer to an ethernet network. The Main Menu will be displayed in the web
browser on the computer simply by entering the IP address of the G60 into the "Address" box on the web browser.
i) TFTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
TFTP PROTOCOL
MESSAGE
MESSAGE
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the G60 over a network. The G60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the G60 contains a list and description of all available files (event records, oscillography, etc.).
j) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
IEC 60870-5-104
PROTOCOL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
COMMUNICATIONS
WEB SERVER HTTP PROTOCOL
HTTP TCP PORT
NUMBER:
80
COMMUNICATIONS
TFTP PROTOCOL
TFTP MAIN UDP PORT
NUMBER:
69
TFTP DATA UDP PORT 1
NUMBER:
0
TFTP DATA UDP PORT 2
NUMBER:
0
COMMUNICATIONS
IEC 60870-5-104 PROTOCOL
IEC 60870-5-104
FUNCTION: Disabled
IEC TCP PORT
NUMBER: 2404
IEC NETWORK
CLIENT ADDRESSES
IEC COMMON ADDRESS
OF ASDU:
0
IEC CYCLIC DATA
PERIOD:
60 s
IEC CURRENT DEFAULT
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
IEC POWER DEFAULT
THRESHOLD: 30000
IEC ENERGY DEFAULT
THRESHOLD: 30000
IEC OTHER DEFAULT
THRESHOLD: 30000
G60 Generator Management Relay
5.2 PRODUCT SETUP
Range: 1 to 65535 in steps of 1
Range: 1 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: Enabled, Disabled
Range: 1 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 1 to 65535 s in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
5
5-25

Advertisement

Table of Contents
loading

Table of Contents