5.5 GROUPED ELEMENTS
5
•
PHS DIST Z1 XFMR VOL CONNECTION: The phase distance elements can be applied to look through a three-phase
delta-wye or wye-delta power transformer. In addition, VTs and CTs could be located independently from one another
at different windings of the transformer. If the potential source is located at the correct side of the transformer, this set-
ting shall be set to "None".
5-86
REV REACH
RCA
Figure 5–39: NON-DIRECTIONAL MHO DISTANCE CHARACTERISTIC
X
RCA
= 80
COMP LIMIT
= 90
DIR RCA
= 80
DIR COMP LIMIT = 90
X
RCA
= 90
COMP LIMIT
= 90
DIR RCA
= 45
DIR COMP LIMIT = 90
Figure 5–40: MHO DISTANCE CHARACTERISTIC SAMPLE SHAPES
G60 Generator Management Relay
X
COMP LIMIT
RCA
837802A1.CDR
X
o
o
o
o
R
X
o
o
o
o
R
5 SETTINGS
R
o
RCA
= 80
o
COMP LIMIT
= 90
DIR RCA
= 80
o
DIR COMP LIMIT = 60
o
R
o
RCA
= 80
o
COMP LIMIT
= 60
DIR RCA
= 80
o
DIR COMP LIMIT = 60
o
R
837722A1.CDR
GE Multilin