B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 47)
ADDR
REGISTER NAME
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F67
Auxiliary Undervoltage 1 Target
7F68
Auxiliary Undervoltage 1 Events
B
7F69
Reserved (7 items)
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000
Tracking Frequency
EGD Fast Production Status (Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
83E1
EGD Fast Producer Exchange 1 Configuration Time
83E3
EGD Fast Producer Exchange 1 Size
EGD Slow Production Status (Read Only) (2 modules)
83F0
EGD Slow Producer Exchange 1 Signature
83F1
EGD Slow Producer Exchange 1 Configuration Time
83F3
EGD Slow Producer Exchange 1 Size
83F4
...Repeated for module number 2
EGD Fast Production (Read/Write Setting)
8400
EGD Fast Producer Exchange 1 Function
8401
EGD Fast Producer Exchange 1 Destination
8403
EGD Fast Producer Exchange 1 Data Rate
8404
EGD Fast Producer Exchange 1 Data Item 1 (20 items)
8418
Reserved (80 items)
EGD Slow Production (Read/Write Setting) (2 modules)
8500
EGD Slow Producer Exchange 1 Function
8501
EGD Fast Producer Exchange 1 Destination
8503
EGD Slow Producer Exchange 1 Data Rate
8504
EGD Slow Producer Exchange 1 Data Item 1 (50 items)
8536
Reserved (50 items)
8568
...Repeated for EGD Exchange 2
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
8A01
Digital Element 1 Name
8A09
Digital Element 1 Input
8A0A
Digital Element 1 Pickup Delay
8A0C
Digital Element 1 Reset Delay
8A0E
Digital Element 1 Block
8A0F
Digital Element 1 Target
8A10
Digital Element 1 Events
8A11
Digital Element 1 Pickup LED
8A12
Reserved (2 items)
8A14
...Repeated for Digital Element 2
8A28
...Repeated for Digital Element 3
8A3C
...Repeated for Digital Element 4
8A50
...Repeated for Digital Element 5
8A64
...Repeated for Digital Element 6
8A78
...Repeated for Digital Element 7
8A8C
...Repeated for Digital Element 8
8AA0
...Repeated for Digital Element 9
8AB4
...Repeated for Digital Element 10
B-32
RANGE
0 to 1
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 65535
---
0 to 65535
0 to 4294967295
0 to 65535
0 to 65535
0 to 4294967295
0 to 65535
0 to 1
0 to 4294967295
50 to 1000
0 to 65535
---
0 to 1
0 to 4294967295
500 to 1000
0 to 65535
---
---
0 to 1
---
0 to 65535
0 to 999999.999
0 to 999999.999
0 to 65535
0 to 2
0 to 1
0 to 1
---
G60 Generator Management Relay
APPENDIX B
UNITS
STEP
FORMAT
---
1
F111
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
---
F001
---
1
F001
---
---
F003
---
1
F001
---
1
F001
---
---
F003
---
1
F001
---
1
F102
---
1
F003
ms
50
F001
---
1
F001
---
---
F001
---
1
F102
---
1
F003
ms
50
F001
---
1
F001
---
---
F001
---
---
F300
---
1
F102
---
---
F203
---
1
F300
s
0.001
F003
s
0.001
F003
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F001
DEFAULT
0 (Definite Time)
100
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0
0
0
0
0 (Disabled)
0
1000
0
0
0 (Disabled)
0
1000
0
0
0
0 (Disabled)
"Dig Element 1"
0
0
0
0
0 (Self-reset)
0 (Disabled)
1 (Enabled)