Remote Inputs - GE L90 Instruction Manual

L90 line current differential system ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

5 SETTINGS
c) LOCAL DEVICES: DEVICE ID FOR TRANSMITTING GSSE MESSAGES
In a L90 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each
GOOSE message is programmed in the
GSSE/GOOSE CONFIGURATION
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the
SETTINGS
CONFIGURATION
TRANSMISSION
In L90 releases previous to 5.0x, these name strings were represented by the
d) REMOTE DEVICES: DEVICE ID FOR RECEIVING GSSE MESSAGES
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE DEVICE
1
MESSAGE
MESSAGE
Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only
those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row)
the exact identification (ID) assigned to those devices.
The
REMOTE DEVICE 1 ETYPE APPID
sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The
REMOTE DEVICE 1 DATASET
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic™
operands. However, GGIO3 data can be read by IEC 61850 clients.
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE INPUT 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Remote Inputs that create FlexLogic™ operands at the receiving relay are extracted from GSSE/GOOSE messages origi-
nating in remote devices. Each remote input can be selected from a list consisting of 64 selections: DNA-1 through DNA-32
and UserSt-1 through UserSt-32. The function of DNA inputs is defined in the IEC 61850 specification and is presented in
GE Multilin
SETTINGS
PRODUCT SETUP
TRANSMISSION
FIXED GOOSE
PRODUCT SETUP
setting.
GSSE
GSSE ID
REMOTE DEVICES
REMOTE DEVICE
Remote Device 1
REMOTE DEVICE
ETYPE APPID: 0
REMOTE DEVICE
DATASET: Fixed
setting is only used with GOOSE messages; they are not applicable to GSSE mes-
setting provides for the choice of the L90 fixed (DNA/UserSt) dataset (that is, containing

REMOTE INPUTS

REMOTE INPUT 1(32)
REMOTE INPUT
1 ID:
Remote Ip
1
REMOTE IN
1 DEVICE:
Remote Device
REMOTE IN
1 ITEM:
None
REMOTE IN
1 DEFAULT
STATE: Off
REMOTE IN
1
EVENTS: Disabled
L90 Line Current Differential System
COMMUNICATIONS
setting.
GOOSE ID
COMMUNICATIONS
IEC 61850 PROTOCOL
RELAY NAME
REMOTE DEVICE 1(16)
Range: up to 20 alphanumeric characters
1 ID:
Range: 0 to 16383 in steps of 1
1
Range: Fixed, GOOSE 1 through GOOSE 8
1
Range: up to 12 alphanumeric characters
Range: 1 to 16 inclusive
1
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32,
Config Item 1 to Config Item 64
Range: On, Off, Latest/On, Latest/Off
Range: Disabled, Enabled
5.8 INPUTS/OUTPUTS
IEC 61850 PROTOCOL
GSSE/GOOSE
setting.
5.8.6 REMOTE INPUTS
5-267