The G60 supports the Distributed Network Protocol (DNP) version 3.0. The G60 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the G60 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the G60 at one time.
The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the
ting is set to "Enabled", the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).
The DNP Channels sub-menu is shown below.
PATH: SETTINGS
PRODUCT SETUP
DNP CHANNELS
MESSAGE
The
settings select the communications port assigned to the DNP protocol for each channel. Once
DNP CHANNEL 1(2) PORT
DNP is assigned to a serial port, the Modbus protocol is disabled on that port. Note that COM1 can be used only in non-
Ethernet UR relays. When this setting is set to "Network - TCP", the DNP protocol can be used over TCP/IP on channels 1
or 2. When this value is set to "Network - UDP", the DNP protocol can be used over UDP/IP on channel 1 only. Refer to
Appendix E for additional information on the DNP protocol.
Changes to the
DNP CHANNEL 1(2) PORT
NOTE
The
DNP NETWORK CLIENT ADDRESS
settings in this sub-menu are shown below.
GE Multilin
DNP MESSAGE FRAGMENT
SIZE: 240
DNP OBJECT 1
DEFAULT VARIATION: 2
DNP OBJECT 2
DEFAULT VARIATION: 2
DNP OBJECT 20
DEFAULT VARIATION: 1
DNP OBJECT 21
DEFAULT VARIATION: 1
DNP OBJECT 22
DEFAULT VARIATION: 1
DNP OBJECT 23
DEFAULT VARIATION: 2
DNP OBJECT 30
DEFAULT VARIATION: 1
DNP OBJECT 32
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED
CONTROL POINTS: 0
DNP TCP CONNECTION
TIMEOUT: 120 s
COMMUNICATIONS
DNP PROTOCOL
DNP CHANNEL 1 PORT:
NETWORK
DNP CHANNEL 2 PORT:
COM2 - RS485
settings will take effect only after power has been cycled to the relay.
settings can force the G60 to respond to a maximum of five specific DNP masters. The
G60 Generator Management Relay
5.2 PRODUCT SETUP
Range: 30 to 2048 in steps of 1
Range: 1, 2
Range: 1, 2
Range: 1, 2, 5, 6
Range: 1, 2, 9, 10
Range: 1, 2, 5, 6
Range: 1, 2, 5, 6
Range: 1, 2, 3, 4, 5
Range: 1, 2, 3, 4, 5, 7
Range: 0 to 32 in steps of 1
Range: 10 to 300 s in steps of 1
IEC 60870-5-104 FUNCTION
DNP CHANNELS
Range: NONE, COM1 - RS485, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
Range: NONE, COM1 - RS485, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
5
set-
5-15