Advertisement

5 SETTINGS
This setting specifies the location of the voltage source with respect to the involved power transformer in the direction
of the zone. The following figure illustrates the usage of this setting. In section (a), Zone 1 is looking through a trans-
former from the delta into the wye winding. Therefore, the Z1 setting shall be set to "Dy11". In section (b), Zone 3 is
looking through a transformer from the wye into the delta winding. Therefore, the Z3 setting shall be set to "Yd1". The
zone is restricted by the potential point (location of the VTs) as illustrated in Figure (e).
PHS DIST Z1 XFMR CUR CONNECTION: This setting specifies the location of the current source with respect to the
involved power transformer in the direction of the zone. In section (a) of the following figure, Zone 1 is looking through
a transformer from the delta into the wye winding. Therefore, the Z1 setting shall be set to "Dy11". In section (b), the
CTs are located at the same side as the read point. Therefore, the Z3 setting shall be set to "None".
See the Theory of Operation chapter for more details, and the Application of Settings chapter for information on calcu-
lating distance reach settings in applications involving power transformers.
(a)
Z3
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = None
Z1 XFRM VOL CONNECTION = Dy11
Z1 XFRM CUR CONNECTION = Dy11
(c)
Z3
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = Yd1
Z1 XFRM VOL CONNECTION = Dy11
Z1 XFRM CUR CONNECTION = None
Figure 5–41: APPLICATIONS OF THE
PHS DIST Z1 REACH: This setting defines the zone reach for the forward and reverse applications. In the non-direc-
tional applications, this setting defines the forward reach of the zone. The reverse reach impedance in non-directional
applications is set independently. The reach impedance is entered in secondary ohms. The reach impedance angle is
entered as the
PHS DIST Z1 RCA
PHS DIST Z1 RCA: This setting specifies the characteristic angle (similar to the 'maximum torque angle' in previous
technologies) of the phase distance characteristic for the forward and reverse applications. In the non-directional appli-
cations, this setting defines the angle of the forward reach impedance. The reverse reach impedance in the non-direc-
tional applications is set independently. The setting is an angle of reach impedance as shown in the distance
characteristic figures shown earlier. This setting is independent from
extra directional supervising function.
PHS DIST Z1 REV REACH: This setting defines the reverse reach of the zone set to non-directional (
setting). The value must be entered in secondary ohms. This setting does not apply when the zone direction is set to
"Forward" or "Reverse".
GE Multilin
o
delta
wye, 330
lag
Z1
o
delta
wye, 330
lag
Z1
PH DIST XFMR VOL/CUR CONNECTION
setting.
G60 Generator Management Relay
5.5 GROUPED ELEMENTS
(b)
o
delta
wye, 330
Z3
Z3 XFRM VOL CONNECTION = Yd1
Z3 XFRM CUR CONNECTION = None
Z1
Z1 XFRM VOL CONNECTION = None
Z1 XFRM CUR CONNECTION = Dy11
(e)
L
1
Zone 3
Zone 1
Z
Z
Z
L1
T
L2
830717A1.CDR
SETTINGS
, the characteristic angle of an
PHS DIST Z1 DIR RCA
lag
L
2
PHS DIST Z1 DIR
5-87