Backup Distance - GE G60 Instruction Manual

Ur series generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

9.1 SETTING EXAMPLE
where A = 28.2, B = 0.1217, and p = 2. Solving for TDM, we have:
Since this element will coordinate with system protections a timed reset is chosen. The element must be blocked for a VT
9
fuse failure. The neutral source will be chosen. Make the following changes in EnerVista UR Setup or through the
GROUPED ELEMENTS
This function provides time-delayed protection for system faults that have not been cleared by system protections and to
provide backup protection for stator faults.
The "Line" source will be used in this example to permit the application of a forward and reverse zone. The memory dura-
tion will be left at the default setting (10 cycles).
Zone 1 will look forward and cover the GSU and the transmission line leaving the station. Zone 3 will look in the reverse
direction and cover the stator winding. Zone 2 will not be used in this example. Both the VTs and the CTs are located on the
low voltage side of the GSU. The transformer vector diagram (see figure 9-1) shows this transformer to be Yd1. Conse-
quently, due to the location of instrument transformers, Dy11 is chosen for both the
settings. There are no transformers in the reverse direction. Therefore "None" is chosen for both of the zone 3
CONNECTION
transformer connection settings. The reach of the zone 1 element will be set at 120% of impedance of the GSU and the
transmission line. In the instance that there are multiple lines and/or multiple generators, the zone 1 reach must be
increased to compensate for the infeed effect.
Transformer impedance
Line impedance
Zone 1 reach
9-6
0.75
TDM
------------------------------------------------------------------------------ -
=
28.2
----------------------------------------------------- -
2.64
----------------------------------- -
1.275 0.329
×
SETTING GROUP 1
PHASE CURRENT
2
V
L
×
---------------
X
=
T
MVA
T
2
V
L
×
------ -
(
)
×
X
15
j75
=
=
+
L
2
V
H
×
(
1.2
Transformer impedance
=
×
(
1.2
j0.162
0.255
j1.276
=
+
+
G60 Generator Management Relay
0.88
=
0.1217
+
2
1
menu:
PHASE TOC1
XFMR VOL CONNECTION
2
(
)
18
×
------------- -
j0.1
j0.162 primary ohms
=
=
200
2
(
)
18
---------------- -
0.255
j1.276 primary ohms
=
+
2
(
138
)
CT ratio
)
×
-------------------- -
Line impedance
+
VT ratio
1600
)
×
-------------- -
17.8 80° secondary ohms
=
157.5
9 APPLICATION OF SETTINGS
(EQ 9.23)
SETTINGS

9.1.10 BACKUP DISTANCE

and
XFMR CUR
(EQ 9.24)
(EQ 9.25)
(EQ 9.26)