5.2 PRODUCT SETUP
The
GOOSE VLAN PRIORITY
have higher priority than other Ethernet data. The
ID for each GOOSE sending device. This value can be left at its default if the feature is not required. Both the
and
PRIORITY
GOOSE ETYPE APPID
The configurable GOOSE settings are shown below:
PATH: SETTINGS...
COMMUNICATIONS
5
CONFIGURABLE
GOOSE 1
The configurable GOOSE settings allow the G60 to be configured to transmit a number of different datasets within IEC
61850 GOOSE messages. Up to eight different configurable datasets can be configured and transmitted. This is useful for
intercommunication between G60 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between G60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the
G60 (DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN
support).
PATH:...TRANSMISSION
CONFIG GSE 1
DATASET ITEMS
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: "GGIO1.ST.Ind1.stVal" and "GGIO1.ST.Ind1.q". The G60 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH:...RECEPTION
CONFIG GSE 1
DATASET ITEMS
The configurable GOOSE settings allow the G60 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to eight different configurable datasets can be configured for reception. This is useful for
intercommunication between G60 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between G60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages.
5-20
setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE messages to
GOOSE ETYPE APPID
settings are required by IEC 61850.
IEC 61850...
CONFIG GSE 1
FUNCTION: Enabled
CONFIG GSE 1 ID:
MESSAGE
GOOSEOut_1
CONFIG GSE 1 DST MAC:
MESSAGE
010CDC010000
CONFIG GSE 1
MESSAGE
VLAN PRIORITY: 4
CONFIG GSE 1
MESSAGE
VLAN ID:
CONFIG GSE 1
MESSAGE
ETYPE APPID:
CONFIG GSE 1
MESSAGE
CONFREV:
CONFIG GSE 1
MESSAGE
DATASET ITEMS
CONFIGURABLE GOOSE 1(8)
ITEM 1:
GGIO1.ST.Ind1.stVal
CONFIGURABLE GOOSE 1(8)
ITEM 1:
GGIO1.ST.Ind1.stVal
G60 Generator Management Relay
setting allows the selection of a specific application
GSSE...
TRANSMISSION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address
Range: 0 to 7 in steps of 1
Range: 0 to 4095 in steps of 1
0
Range: 0 to 16383 in steps of 1
0
Range: 0 to 4294967295 in steps of 1
1
Range: 64 data items; each can be set to all valid MMS
data item references for transmitted data
CONIFIG GSE 1(64) DATA TIMES
Range: all valid MMS data item references for
transmitted data
CONIFIG GSE 1(64) DATA ITEMS
Range: all valid MMS data item references for
transmitted data
5 SETTINGS
GOOSE VLAN
CONFIGURABLE GOOSE 1(8)
ITEM 1(64)