The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
Table 5–2: DATA LOGGER STORAGE CAPACITY EXAMPLE
SAMPLING RATE
CHANNELS
15 ms
1000 ms
60000 ms
3600000 ms
Changing any setting affecting data logger operation will clear any data that is currently in the log.
NOTE
DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to "Continu-
ous", the data logger will actively record any configured channels at the rate as defined by the
GE Multilin
DATA LOGGER
DATA LOGGER MODE:
Continuous
DATA LOGGER TRIGGER:
Off
DATA LOGGER RATE:
60000 ms
DATA LOGGER CHNL
Off
DATA LOGGER CHNL
Off
DATA LOGGER CHNL 16:
Off
DATA LOGGER CONFIG:
0 CHNL x
0.0 DAYS
DAYS
1
0.1
8
0.1
9
0.1
16
0.1
1
0.7
8
0.1
9
0.1
16
0.1
1
45.4
8
5.6
9
5
16
2.8
1
2727.5
8
340.9
9
303
G60 Generator Management Relay
Range: Continuous, Trigger
Range: FlexLogic™ operand
Range: 15 to 3600000 ms in steps of 1
Range: Off, any FlexAnalog parameter. See Appendix A:
1:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
2:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
Range: Not applicable - shows computed data only
STORAGE CAPACITY
954 s
120 s
107 s
60 s
65457 s
8182 s
7273 s
4091 s
3927420 s
490920 s
436380 s
254460 s
235645200 s
29455200 s
26182800 s