B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 47)
ADDR
REGISTER NAME
A902
Frequency Rate of Change 1 Min
A903
Frequency Rate of Change 1 Max
A904
Frequency Rate of Change 1 Pickup Delay
A905
Frequency Rate of Change 1 Reset Delay
A906
Frequency Rate of Change 1 Block
B
A907
Frequency Rate of Change 1 Target
A908
Frequency Rate of Change 1 Events
A909
Frequency Rate of Change 1 Source
A90A
Frequency Rate of Change 1 Trend
A90B
Frequency Rate of Change 1 Pickup
A90C
Frequency Rate of Change 1 OV Supervision
A90D
Frequency Rate of Change 1 Reserved (3 items)
A910
...Repeated for Frequency Rate of Change 2
A920
...Repeated for Frequency Rate of Change 3
A930
...Repeated for Frequency Rate of Change 4
Restricted Ground Fault (Read/Write Grouped Setting) (6 modules)
A960
Restricted Ground Fault 1 Function
A961
Restricted Ground Fault 1 Source
A962
Restricted Ground Fault 1 Pickup
A963
Restricted Ground Fault 1 Slope
A964
Restricted Ground Fault 1 Delay
A965
Restricted Ground Fault 1 Reset Delay
A966
Restricted Ground Fault 1 Block
A967
Restricted Ground Fault 1 Target
A968
Restricted Ground Fault 1 Events
A969
...Repeated for Restricted Ground Fault 2
A972
...Repeated for Restricted Ground Fault 3
A97B
...Repeated for Restricted Ground Fault 4
A984
...Repeated for Restricted Ground Fault 5
A98D
...Repeated for Restricted Ground Fault 6
IEC 61850 received analog settings (read/write)
AA00
IEC 61850 GOOSE analog 1 default value
AA02
IEC 61850 GOOSE analog input 1 mode
AA03
IEC 61850 GOOSE analog input 1 units
AA05
IEC 61850 GOOSE analog input 1 per-unit base
AA07
...Repeated for IEC 61850 GOOSE analog input 2
AA0E
...Repeated for IEC 61850 GOOSE analog input 3
AA15
...Repeated for IEC 61850 GOOSE analog input 4
AA1C
...Repeated for IEC 61850 GOOSE analog input 5
AA23
...Repeated for IEC 61850 GOOSE analog input 6
AA2A
...Repeated for IEC 61850 GOOSE analog input 7
AA31
...Repeated for IEC 61850 GOOSE analog input 8
AA38
...Repeated for IEC 61850 GOOSE analog input 9
AA3F
...Repeated for IEC 61850 GOOSE analog input 10
AA46
...Repeated for IEC 61850 GOOSE analog input 11
AA4D
...Repeated for IEC 61850 GOOSE analog input 12
AA54
...Repeated for IEC 61850 GOOSE analog input 13
AA5B
...Repeated for IEC 61850 GOOSE analog input 14
AA62
...Repeated for IEC 61850 GOOSE analog input 15
AA69
...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
AA80
Default GOOSE/GSSE Update Time
AA81
IEC 61850 GSSE Function (GsEna)
AA82
IEC 61850 GSSE ID
B-38
RANGE
20 to 80
20 to 80
0 to 65.535
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 5
0 to 2
0.1 to 15
0.1 to 3
0 to 1
0 to 1
0 to 5
0 to 30
0 to 100
0 to 600
0 to 600
---
0 to 2
0 to 1
–1000000 to 1000000
0 to 1
---
0 to 999999999.999
1 to 60
0 to 1
---
G60 Generator Management Relay
APPENDIX B
UNITS
STEP
FORMAT
Hz
0.01
F001
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F167
---
1
F224
Hz/s
0.01
F001
pu
0.001
F001
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
%
1
F001
s
0.01
F001
s
0.01
F001
---
---
F001
---
1
F109
---
1
F102
---
0.001
F060
---
1
F491
0 (Default Value)
---
---
F207
---
0.001
F060
s
1
F001
---
1
F102
---
---
F209
DEFAULT
4500
6500
0
0
0
0 (Self-reset)
0 (Disabled)
0 (SRC 1)
0 (Increasing)
50
700
0
0 (Disabled)
0 (SRC 1)
80
40
0
0
0
0 (Self-reset)
0 (Disabled)
1000
(none)
1
60
1 (Enabled)
"GSSEOut"
GE Multilin