GE G60 Instruction Manual page 245

Ur series generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5 SETTINGS
SETTING
ACCDNT ENRG
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
AND
ACCDNT ENRG
BLOCK:
Off = 0
SETTING
ACCDNT ENRG
SOURCE:
IA
IB
IC
VT CONNECTION
WYE
DELTA
VAG - VBG
VAB
VBG - VCG
VBC
VCG - VAG
VCA
SETTING
ACCDNT ENRG
OFFLINE:
Off = 0
SETTING
ACCDNT ENRG
ARMING MODE:
UV or Offline = 1
Figure 5–87: ACCIDENTAL ENERGIZATION SCHEME LOGIC
GE Multilin
SETTINGS
ACCDNT ENRG OC
PICKUP:
RUN
IA
> Pickup
RUN
OR
IB
> Pickup
RUN
IC
> Pickup
SETTINGS
ACCDNT ENRG UV
PICKUP:
RUN
VAB < Pickup
RUN
AND
VBC < Pickup
RUN
AND
VCA < Pickup
OR
AND
G60 Generator Management Relay
5.5 GROUPED ELEMENTS
AND
5 s
OR
0.25 s
5
FLEXLOGIC OPERANDS
ACCDNT ENRG OP
ACCDNT ENRG DPO
FLEXLOGIC OPERAND
ACCDNT ENRG ARMED
830004A3.CDR
5-147

Advertisement

Table of Contents
loading