5 SETTINGS
The
setting is the DNP slave address. This number identifies the G60 on a DNP communications link. Each
DNP ADDRESS
DNP slave should be assigned a unique address.
The
DNP TCP CONNECTION TIMEOUT
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the G60. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the
effect.
NOTE
f) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
PRODUCT SETUP
DNP / IEC104
POINT LISTS
MESSAGE
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
BINARY INPUT / MSP
POINTS
MESSAGE
MESSAGE
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
ANALOG INPUT / MME
POINTS
MESSAGE
MESSAGE
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP /
IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point
NOTE
are ignored.
GE Multilin
setting specifies a time delay for the detection of dead network TCP connections. If
DNP TCP CONNECTION TIMEOUT
COMMUNICATIONS
DNP / IEC104 POINT LISTS
BINARY INPUT / MSP
POINTS
ANALOG INPUT / MME
POINTS
COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off
COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off
G60 Generator Management Relay
5.2 PRODUCT SETUP
setting for the changes to take
Range: see sub-menu below
Range: see sub-menu below
BINARY INPUT / MSP POINTS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
ANALOG INPUT / MME POINTS
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
5
5-17