Special Programming Settings

Clear Panel Memory
50002
(Default = n/a) It is recommended that you clear memory on all
newly installed panels before programming. Clearing memory
deletes setup values and resets all values to factory defaults.
To Clear Panel Memory:
1.
Enter program mode.
2.
Enter the installer code.
3.
Enter item number 50002.
ƒ . Wait about a minute until touchpads
4.
Press 99 and then
return to their default displays.
Note
Since all programming information is contained in mem-
ory, clearing memory deletes all existing programming
information except dealer values (if any).
Reviewing (List) Settings
00000
(Default = n/a) An easy way of listing all programming settings
and their values is provided. You can list all settings, or settings
starting at a selected item number.
To list all Settings:
1.
Once in program mode enter the item number (00000).
ƒ to start listing settings from the beginning
2.
Press
or
enter the item number you wish to start at and press
Touchpads will flash each of the item numbers and values
(if not protected by dealer password).
‚ at any time to exit this menu.
3.
Press
Note
Displayed setting values may be viewed but not changed
using this procedure.
Advent Commercial Fire System

Partitions/General Partition Settings

Partitions Act As Areas
17127
(Default = off) Choose whether or not to treat partitions as areas.
If treated as areas:
‰ Zones, touchpads, schedules, programming options, etc.,
belong to areas instead of partitions.
‰ Users may "jump" from one area to another area using an
alphanumeric touchpad.
‰ The word "partition" will be changed to "area" wherever
it is spoken, displayed, or printed.
To turn Areas On/Off:
Once the item number has been entered, enter
ƒ
off. Press
to apply the new setting.
Touchpad Redirect Reset Time
17035
(Default = 10 seconds) This setting allows you to select the length
(in seconds) of inactivity (no menu activity) before a "jumped"
touchpad returns to its assigned area.
To set Touchpad Redirect Reset Time:
1.
Once in program mode enter the item number.
2.
Enter the desired length (5–60) and press
Global Account Reporting
ƒ .
17093
(Default = off) The setting enables the panel to report events as a
system.
When set to on:
‰ The panel will use system account and area numbers when
reporting events.
‰ The panel will only perform one automatic phone test (not
one for each partition/area).
To turn Global Account Reporting On/Off:
Once the item number has been entered, enter
ƒ
off. Press
to apply the new setting.
Partitions Enabled
xx068
(Defaults = Partition/Area 1 - on, all others off) Choose whether
or not to enable the partition/area. Partition/Area 1 is always
enabled.
To turn a Partition/Area On/Off:
Once the item number has been entered, enter
ƒ
off. Press
to apply the new setting.
(Partitions-General Partition Settings)
1
for on, or
(Partitions-General Partition)
ƒ .
(Partitions-General Partition)
1
for on, or
(Partitions-General Partition Settings)
1
for on, or
0
for
0
for
0
for
17