Exit Delay
xx004
(Default = 32 seconds) Enter the length of the standard exit delay
(in seconds). This is the number of seconds the user has to exit the
premises through a standard delay door after arming the system.
If the user trips a zone after this time period has expired, an alarm
is generated.
To set the Exit Delay:
Once the item number has been entered, enter the number of
seconds (24–120) users will have to exit the premises after arming
ƒ
the system. Press
to apply the new setting.
Extended Delay
xx005
(Default = 2 minutes) Enter the length of the extended delay. The
extended delay time determines how much time (in minutes) the
user has to enter or exit the premises through an extended delay
door without causing an alarm.
To set the Extended Delay:
Once the item number has been entered, enter the number of
minutes (1–10) for the extended delay and press
Early Termination Delay
xx101
(Default = off) If on, the system will arm as soon as it detects a
delay zone closing. Once a person leaves through an exit delay
door and the door closes, the exit delay is terminated and the
system is armed.
Note
Cannot be used with One-Time Reset Enabled setting
(xx102).
To turn Early Termination Delay On/Off:
Once the item number has been entered, enter
0
setting on or
to turn it off. Press
One-Time Reset Enabled
xx102
(Default = off) If on, the system will allow a one-time reset of the
standard exit delay. If a user leaves through a delay door and the
door closes, they may re-enter through the door within the exit
delay time period and the system will reset the exit delay.
Note
Cannot be used with Early Termination Enabled setting
(xx101).
To turn One-Time Reset Enabled On/Off:
Once the item number has been entered, enter
0
setting on or
to turn it off. Press
Advent Commercial Fire System
(Partitions-Arming)
(Partitions-Arming)
ƒ
.
(Partitions-Arming)
1
to turn the
ƒ
to apply the new setting.
(Partitions-Arming)
1
to turn the
ƒ
to apply the new setting.
Fast Beep Duration
xx006
(Default = 10 seconds) Enter the length of time (in seconds) that
fast beeps will sound during the last portion of the exit delay to
signal the delay is ending.
To set the Fast Beep Duration:
Once the item number has been entered, enter the number of
seconds (5–15) fast beeps will sound before the end of the delay
ƒ
and press
.
Fast Beeps at End of Exit Delay Only
xx100
(Default = on) If on, only the fast beeps at the end of the exit
delay will sound. If off, slow exit delay beeps will sound followed
by the fast beeps at the end of the delay.
To turn Fast Beeps at End of Exit Delay Only On/
Off:
Once the item number has been entered, enter
0
setting on or
to turn it off. Press
Beeps During Standard Entry Delay Only
xx103
(Default = off) If on, beeps only sound during the standard entry
delay. If off, beeps sound during all segments of an entry delay
including standard, extended, and twice extended.
To turn Beeps During Standard Entry Delay Only
On/Off:
Once the item number has been entered, enter
0
setting on or
to turn it off. Press
(Partitions-Arming)
(Partitions-Arming)
1
to turn the
ƒ
to apply the new setting.
(Partitions-Arming)
1
to turn the
ƒ
to apply the new setting.