Connecting Superbus 2000 Modules And Touchpads; Superbus 2000 Touchpads - GE Advent Installation Instructions Manual

Commercial fire system
Table of Contents

Advertisement

SECONDARY EXPANSION
CARD CONNECTOR
CONTROL PANEL
CIRCUIT BOARD
Figure 4. Installing an Expansion SnapCard into one of
the two SnapCard Connectors
Connect all necessary input and/or output wiring using the
Installation Instructions included with the SnapCard(s).
Note
Once the 24V Smoke Loop SnapCard is installed, the
panel onboard smoke loop becomes a 24V smoke loop
(panel terminals 21 and 22).
If the 24V Smoke Loop SnapCard is used, the panel and
snapcard 2-wire smoke loops are not compatible with the
Sentrol (ESL) 429AT smoke detector.
Connecting SuperBus 2000 Modules and
Touchpads
Up to 31 SuperBus 2000 devices (combinations of touch-
pads and modules) can be used on each of the two SuperBus
connectors for a total of up to 62 devices. These modules
connect to the panel via a 4-wire digital data bus and may
be located inside, next to, or away from the panel cabinet
(see Figure 5). The panel cabinet may accommodate up to:
‰ 3 SuperBus 2000 HIM/HOM modules,
‰ 1 Voice Siren 25/70 Volt Converter Card,
‰ and 2 AC Power Transformers.
To wire SuperBus 2000 devices to the SuperBus connectors
you must use the Panel SuperBus Wiring Harnesses (49-
462) included with the accessory kit. You must splice all
SuperBus 2000 module and touchpad wiring to the wires on
these harnesses. Both SuperBus connectors are the same,
and any combination of SuperBus devices (up to 31) may
be wired to either connector. When all of the SuperBus
2000 devices are wired, plug each wiring harness into a
SuperBus connector.
Note
The +12 VDC (RED) lead on the SuperBus wiring harness
is current limited to 650 mA. If the total current draw for all
devices on either SuperBus connector exceeds 650 mA,
another power source must be used—such as Terminal 4
(+12V) or an external + 12V power supply.
Advent Commercial Fire System
PRIMARY EXPANSION
CARD CONNECTOR
ALIGN BOARD
HOLES WITH
STANDOFFS
EXPANSION CARD
8543G86B.DSF
.
(2)
SPACE FOR
2ND TRANSFORMER
8543264A.DSF
Figure 5. Mounting Devices in Panel Cabinet
Important !
Use the SuperBus connectors (BUS 1 and BUS 2) head-
ers for either fire or burglary applications. Do not mix fire
and burglary bus devices on either header. All bus device
inputs and outputs must be used for either fire or burglary
applications. Do not mix fire and burglary applications on
inputs and outputs of any bus device.

SuperBus 2000 Touchpads

‰ 2x20 LCD Alphanumeric Touchpad (60-803-01)
‰ 2x20 VFD Alphanumeric Touchpad (60-804-01)
‰ 2x20 VFD Fire Alphanumeric Touchpad (60-810-04)
(Commercial Fire Panels Only)
Connect SuperBus 2000 touchpads to the desired SuperBus
connector as shown in Figure 6. For mounting instructions
please see the specific touchpad Installation Instructions.
PANEL CABINET
(COVER NOT SHOWN)
MOUNTED
TRANSFORMER
MOUNTED
VOICE SIREN 25/70
VOLT CONVERTER CARD
SPACE FOR 2ND HIM/HOM/DUAL
PHONE LINE MODULE
MOUNTED HIM/HOM/DUAL
PHONE LINE MODULE
SPACE FOR 3RD
HIM/HOM/DUAL PHONE LINE MODULE
9