Voice Siren 25/70 Volt Converter Card (60-773); Connecting Detection Devices To Panel Zone Inputs; Connecting Speakers - GE Advent Installation Instructions Manual

Commercial fire system
Table of Contents

Advertisement

DRIVER BOARD
TERMINAL STRIP
DATA IN
CLOCK
LOAD
DATA OUT
+12V
DRIVE
DRIVE
DRIVE
RETURN
5
1
2
3
4
WIRING HARNESS 49-462
Figure 13.Connecting an LED Module (Driver Board)

Voice Siren 25/70 Volt Converter Card (60-773)

Mount the card in the panel cabinet in the area shown in
Figure 5, and as described in the specific Installation
Instructions. Wire the card to the panel and speakers as
shown in Figure 14.
Note
70 volt wiring and supervision is shown. For 25 volt wiring,
connect speakers to COMMON and 25V terminals, then
jump +SUPERVISION to 25V terminal.
PANEL
TERMINALS
VOICE
VOICE
SIREN
SIREN
9
10
VOICE SIREN CONVERTER
+
SUPER-
VISION
+
-
4 OHMS
UL-LISTED SPEAKERS
(PARALLEL)
9715g03d.dsf
Figure 14.Connecting the Voice Siren 25/70 Volt
Converter Card
Note
Separate in and out conductors must be used at each
speaker. Do not loop a single wire around each terminal.
*) Not investigated by UL.
12
BUS A
BUS B
GND
ZONE 1
COM
6
7
8
9
10
BLACK (GND)
WHITE (BUS B)
GREEN (BUS A)
RED (+12 VDC)
PANEL SUPERBUS
CARD TERMINALS
COM-
70V
25V
MON
2K OHM 5 WATT
EOL RESISTOR
ASSEMBLY 49-482
(LOCATE AT
LAST DEVICE)
Connecting Detection Devices to Panel
Zone Inputs
Important !
Use onboard panel inputs and outputs for all fire applica-
tions only. Do not mix fire and burglary circuits.
Connecting 2-Wire Smoke Detectors
Panel terminals 21 and 22 are set up to accept the following
12 VDC 2-wire smoke detectors.
‰ System Sensor models 2100S, 2100TS, 2100D, 2100TD,
2400, or 2400TH.
‰ Sentrol (ESL) models 429AT, 521B, or 521BXT
Panel terminals 21 and 22 can handle up to 20 smoke detec-
tors with 120 uA maximum idle current per detector. Maxi-
mum total loop current in alarm condition is 100 mA.
*
Connect one or more 2-wire smoke detectors to the panel as
shown in Figure 15.
Note
If the 24V Smoke Loop SnapCard is used, the panel and
snapcard 2-wire smoke loops are not compatible with the
Sentrol (ESL) 429AT smoke detector.
( I N S T A L L A T L A S T D E V I C E )
+ O R 2 4 V D C W I T H 2 4 V S M O K E L O O P
E X P A N S I O N S N A P C A R D I N S T A L L E D .
Figure 15.Connecting 2-Wire Smoke Detectors

Connecting Speakers

The panel provides one speaker driver output for intrusion
(steady), fire (temporal 3), and auxiliary (on-off-on-off)
alarm sounds.
The output can drive a single 8-ohm speaker or multiple
speaker circuit of 4- to 8-ohms (as shown in the following
speaker wiring diagrams). Comparable speakers are
described below and on the following page.
$87,21
To avoid damage the panel speaker output, do not make
speaker connections with the panel powered up.
2 - W I R E
S M O K E L O O P
+ 1 2 V
+
S W
+
2 1
2 2
L I S T E D 2 - W I R E ,
+
1 2 V
S M O K E / H E A T
+
D E T E C T O R
( U S E I N - A N D - O U T
+
[ D A I S Y - C H A I N ]
M U L T I P L E D E V I C E
W I R I N G
M E T H O D S
O N L Y . )
2 . 0 K O H M
E O L R E S I S T O R
4 9 - 4 6 7 o r 4 9 - 4 5 4