To acheive 24-hour backup Total Standby Current Draw must not exceed 650mA with 1 battery, 1350mA with 2 batteries, or
2.0A with 3 batteries for UL systems
Total Maximum Alarm Current Draw (must not exceed 5.5A)

Determining Maximum Panel Wire Length

Example:
Using 22 gauge wire to connect the following devices on
one wire run (length of cable):
Device Current Draw (see note)
1- Hardwire 2-Line Alpha Touchpad = 120 mA
1- RF Transceiver Module = 50 mA
1-8Z Hardwire Input Module = 35 mA
Total Device Current Draw = 205 mA
Find the total device current draw in the table and match the
wire type used. In this example, the maximum recom-
mended wire length is about 154 feet. For longer lengths,
use a larger gauge wire.
Note
For self- or remotely-powered devices, the maximum rec-
ommended wire length is 4,000 feet using 22 gauge or
larger wire.
Table A.2 Max. Wire Length Recommendations*
(Feet)
Total
Device
22 Gauge
18 Gauge
Current
(AWG)
(AWG)
Draw
(mA)
100
616
1,562
200
308
300
206
400
154
500
124
600
104
700
88
800
78
64
Table A.1 System Hardwire Devices (Continued)
Qty.
Standby Current Draw
10 mA
+ 2.5 mA per zone used
+ 7 mA per smoke loop used
+ 34 mA per relay used
10 mA
+ 2.5 mA per zone used
+ 7 mA per smoke loop used
6 mA
+ 34 mA per relay used
16 Gauge
14 Gauge
(AWG)
(AWG)
2,486
3,936
782
1,244
1,968
522
830
1314
392
622
982
314
500
792
262
416
653
224
356
564
196
312
492
Standby
Current
Subtotal
185 mA
230 mA
130 mA
Total
Table A.2 Max. Wire Length Recommendations*
(Feet)
Total
Device
22 Gauge
18 Gauge
Current
(AWG)
(AWG)
Draw
(mA)
900
70
174
1000
61
156
1100
56
142
1200
54
130
1300
48
120
1400
44
112
1500
42
104
1600
40
1700
36
1800
34
1900
32
2000
30
2100
29
2200
28
2300
27
2400
26
2500
25
2600
24
2700
23
2800
22
2900
21
3000
20
*Two volt maximum loop voltage drop.
Maximum
Maximum
Alarm
Current Draw
Current
Subtotal
16 Gauge
14 Gauge
(AWG)
(AWG)
278
438
250
394
226
358
208
330
192
304
178
282
166
264
98
156
246
92
146
232
88
138
216
82
132
208
78
126
198
74
120
188
72
114
180
68
108
172
66
104
164
64
100
158
60
96
152
58
92
146
56
90
140
54
86
136
52
84
132