Partitions/X10

X10 House Code 1
xx022
(Default = Partition/Area Number) The house code is a number
from 1 to 16 (representing A–P) used to communicate panel
signals to line carrier devices such as X10 Lamp, Appliance, and
Universal Modules. You can have up to two house codes per
partition/area.
Enter the panel house code setting used for the first 16 X10 line
carrier devices. The system commands "All Lights On/Off" or
"All Units On/Off" control only modules with House Code 1
(within respective partition/area). See Table B.5 on page 97 for
information on defaults.
Entering House Code 1:
Once the item number has been entered, enter the desired house
ƒ
code (1–16). Press
to apply the new setting.
X10 House Code 2
xx023
(Default = Partition/Area Number + 8) Enter the panel house code
setting used for the last 16 X10 line carrier devices within
respective partition/area. See for information on defaults.
Entering House Code 2:
Once the item number has been entered, enter the desired house
ƒ
code (1–16). Press
to apply the new setting.
Non X10 Output 1 (menu output 33)
Non X10 Output 2 (menu output 34)
Non X10 Output 3 (menu output 35)
Non X10 Output 4 (menu output 36)
Non X10 Output 5 (menu output 37)
Non X10 Output 6 (menu output 38)
Non X10 Output 7 (menu output 39)
Non X10 Output 8 (menu output 40)
1: xx049, 2: xx050, 3: xx051, 4: xx052,
5: xx053, 6: xx054, 7: xx055, 8: xx056
(Default = none) There are 40 menu outputs per partition/area.
The first 32 are X10 outputs, the last 8 are non X10 outputs. All
X10 outputs (menu outputs 1-32) are automatically linked to X10
devices. Non X10 outputs (menu outputs 33-40) must be linked to
a programmable output in order to control a light or device.
Note
All menu outputs must be programmed (learned) into the
panel before they will function. See "Fixed Output Set-
tings" on page 42 for more information.
Linking Non X10 Outputs:
1.
Enter the item number for the desired non X10 output.
2.
Enter the desired programmable output number (1–100),
ƒ to confirm the selection.
then press
Advent Commercial Fire System

Partitions/Reporting

Light Control
(Partitions-X10)
xx069
(Default = off) If on, users must enter a valid access code before
controlling lights. If off, an access code is not required for light
control.
To turn Light Code On/Off:
Once the item number has been entered, enter
code required), or
Device Control
xx070
(Default = off) If on, users must enter a valid access code before
controlling devices. If off, an access code is not required for
device control.
To turn Device Control On/Off:
(Partitions-X10)
Once the item number has been entered, enter
code required) or
Latchkey Access
xx071
(Default = off) If on, users must enter a valid access code before
accessing the Latchkey setting. If off, an access code is not
required to access the Latchkey setting. For more information on
Latchkey, please see the User's Manual.
To turn Latchkey Access On/Off:
Once the item number has been entered, enter
code required) or
Report Partition Events to Central Station
xx088
(Partitions-X10)
(Default = on) If on, the panel will report partition/area events to
the central station.
To turn Reporting Partition Events to Central
Station On/Off:
Once the item number has been entered, enter
area event reporting on or
the new setting.
Cancel Event Cancels Report
xx089
(Default = on) If on, the panel will cancel the sending of an alarm
report (to central station) if the event is canceled before the delay
between generated standard alarm and alarm reporting (xx013)
expires.
To turn Cancel Event Cancels Report On/Off:
Once the item number has been entered, enter
setting on (canceled event cancels report) or
ƒ
to apply the new setting.
(Partitions-Reporting)
1
0
ƒ
for off. Press
to apply the new setting.
(Partitions-Reporting)
1
0
ƒ
for off. Press
to apply the new setting.
(Partitions-Reporting)
1
0
ƒ
for off. Press
to apply the new setting.
(Partitions-Reporting)
1
0
turn reporting off. Press
(Partitions-Reporting)
1
0
to turn it off. Press
for on (access
for on (access
for on (access
to turn partition/
ƒ
to apply
to turn the
21