Table 2. UL 609 Listed System Settings (Continued)
Feature
Feature
No.
xx102
One-Time Reset Enabled
17034
Phone Test Interval
17036
AC Stable Time
17041
Hours to Delay Before
Reporting AC Failure
17049
RF Supervisory Time A
17069
No Phone Line Attached
17072
Enable RF Jam Detect
17073
Battery Test Interval
17076
Commercial or Residential
Installation
17078
Detect Receiver Failure
17079
Alarm Messages Played at
High Volume
17096
Report System Events
47004
Zone Attributes (edit zones)
xx = Two digit partition number.
yy = Two digit non-pager phone number.
Control Units for Fire Protective Signaling Devices (UL
864)
Basic system using:
‰ Commercial Fire (60-562-03 or 60-562-06) Control Panel
‰ 24 VAC output, 100 VA Class I, 110 VAC, 60 Hz (60-830)
Line Carrier AC Power Transformer
plus:
‰ SuperBus 2000 Fire Alphanumeric Touchpad (60-810-04)
‰ SuperBus 2000 Dual Phone Line Module (60-768)
‰ UL 864 listed 4-8 ohm, 15W Speaker
Hardwire 2-Wire Smoke Detector (Compatibility Identifier
#60-562, 20 per loop maximum.):
System Sensor models 2100S, 2100TS, 2100D, 2100TD, 2400,
or 2400T added (learned) into
Zone Type 80
Sentrol models 429AT, 521B, or 521BXT added (learned) into
Zone Type 80
Table 3. UL 864 Listed System Settings
Feature
Feature
No.
xx002
Siren Time Out
yy004
Comm Format
xx081
Disable Siren
xx083
Tamper Signals from Fire
Zones are Alarms
xx085
Enable Police Panic Keys
xx086
Enable Auxiliary/Medical
Panic Keys
2
Table 3. UL 864 Listed System Settings (Continued)
Feature
Required Setting
0-Off
xx087
1 Day
xx088
90 sec. maximum
xx091
8 hours (or less)
xx092
4 hours
xx097
0-Off
xx102
1-On
17034
1=4 hours
17036
1-Commercial
17041
1-On
17049
1-On (High)
17069
17072
1-On
17073
N/A
17076
17078
17079
17084
17096
17099
17111
17126
47004
xx = Two digit partition number.
yy = Two digit non-pager phone number.
The basic system may also include:
‰ SuperBus 2000 Commercial RF Transceiver (60-856-95)
‰ Wireless Smoke Sensor (60-849-01-95) added (learned)
‰ SuperBus 2000 Printer Automation Module (60-854) for
Required Setting
‰ AL602 ITI NAC Power Supply (13-522)
‰ 24V Smoke Loop SnapCard (60-767)
6 min. minimum
‰ Universal Fire Transmitter (UFT) (60-917-95)
0 Contact ID
Zone Types 11 (Extended Entry/Exit Delay), 12 (Twice
1-On
Extended Delay), 15 (Instant Interior), 17 (Instant Interior),
0-off
18 Instant Interior), 19 (Delayed Interior), 20 (Delayed Inte-
rior), 24 (Local Instant Auxiliary), and 25 (Local Special
Chime) are not to be used as primary protection circuits in
1-On
UL 864 listed systems and are for supplementary use only.
1-On
Zone Types 27, 28, and 32 (Custom Outputs) may not be
used in UL 864 listed systems.
Feature
No.
Enable Fire Panic Keys
Report Partition/Area Events
to Central Station
Print Partition/Area Events
Enable Auto Force Arming
Exterior Arming Verification
One-Time Reset Enabled
Phone Test Interval
AC Stable Time
Hours to Delay Before
Reporting AC Failure
RF Supervisory Time A
No Phone Line Attached
Enable RF Jam Detect
Battery Test Interval
Commercial or Residential
Installation
Detect Receiver Failure
Alarm Messages Played at
High Volume
First Disarm Silences Fire
Alarmd and Second Disarm
Cancels the Alarm
Report System Events
Print System Events
Time Fire Alarm is Silenced
Unsilence Alarm after
Silencing Period
Zone Attributes (edit zones)
for use with listed wireless signaling devices
into Zone Type 80
use with a listed printer
Required Setting
0-Off
1-On
1-On
0-Off
0-Off
0-Off
1 Day
90 sec. maximum
8 hours (or less)
4 hours
0-Off
1-On
1-4 hours
1-Commercial
1-On
1-On (High)
1-On
1-On
1-On
30 sec. (or less)
1-On
N/A
Advent Commercial Fire System