Partitions/Alarms - GE Advent Installation Instructions Manual

Commercial fire system
Table of Contents

Advertisement

Partitions/Alarms

Daily Trouble Reporting Time
xx001
(Default = 12:00) This is the time of day when the system will
annunciate any existing trouble conditions. For Advent
Commercial Fire and Burglary panels, trouble(s) are annunciated
every 4 hours. If the Daily Trouble Reporting time is set at 12:00
pm then the system will announce trouble(s) at 12:00 pm, 4:00
pm, 8:00 pm, 12:00 am, 4:00 am, and 8:00 am.
To set the Daily Trouble Reporting Time:
Once the item number has been entered, enter the 4-digit time
(00:00–23:59) in 24 hour format and press
Note
The Enable Daily Reporting of Partition Trouble setting
(xx108) must be set to "on" for this setting to work.
Enable Daily Reporting of Partition Trouble
xx108
(Default = on) Enables annunciation of all trouble conditions at
LTime (
To turn Enable Daily Reporting of Partition
Trouble on/off:
Once the item number has been entered, enter
0
second delay), or
for off (no delay). Press
setting.
Siren Time Out
xx002
(Default = 16 Minutes) This is the number of minutes that the
alarm siren is allowed to sound. The siren will silence when this
value is reached.
To set Siren Sound Time:
Once the item number has been entered, enter the number of
minutes (01–30) you wish the siren to sound and press
Generate Alarm for Unarmed Tamper Signals
xx079
(Default = off) This setting determines whether a tamper alarm is
generated for a zone that is not armed (applies to non-fire zones
only). If on, a zone tamper alarm is generated when a zone tamper
is detected in any arming level. If off, an alarm is only generated
when the zone is in an active level.
To turn Alarm for Unarmed Tamper Signals On/
Off:
Once the item number has been entered, enter
0
all levels), or
for off (alarm in active levels). Press
the new setting.
Advent Commercial Fire System
Tamper Signals from Fire Zones are Alarms
(Partitions-Alarms)
xx083
(Default = off) This setting enables the panel to generate a tamper
alarm (in addition to a trouble report) when tampering of a fire
zone is detected.
To set the Fire Tamper Response to On/Off:
Once the item number has been entered, enter
generated) or
the new setting.
ƒ
.
Enable Keystroke Violation Alarm
xx076
(Default = off) This setting enables keypad tamper. When on, the
panel will generate a police alarm when it detects four or more
incorrect access code entry attempts that do not include a valid
access code. A tamper report is also sent to the central station.
(Partitions-Alarms)
To turn Enable Keystroke Violation Alarm On/Off:
Once the item number has been entered, enter
alarm and report) or
1
for on (15-
No Activity Tripped After
ƒ
to apply the new
xx009
(Default = not active) This setting allows you to select the length
of time (in hours) the panel will wait after not detecting any
activity before initiating a no-activity pre-alarm. Once a no-
activity pre-alarm is initiated the panel will wait until the time in
the Delay Between No Activity Trip and Alarm setting (xx010)
(Partitions-Alarms)
expires before generating an alarm.
To set the No Activity Tripped After time:
1.
2.
ƒ
.
Delay Between No Activity Trip and Alarm
xx010
(Partitions-Alarms)
(Default = 5 Minutes) This setting allows you to select the length
of time (in minutes) allowed after the No Activity Tripped After
setting (xx009) time has expired. If no activity is generated during
this time the panel sends a report to the central station. If the
user(s) generate activity within this delay period no report will be
sent.
To set the Delay Between No Activity Trip and
Alarm:
1
for on (alarm in
Once the item number has been entered, enter the number of
ƒ
to apply
minutes (1–10) you wish the panel to wait before sending a
report. Press
0
for off (alarm not generated). Press
0
for off. Press
Once the item number has been entered, enter the number
of hours (1–24) you wish the panel to wait before initiat-
ing a no-activity pre-alarm, or
ƒ to apply the new setting.
Press
ƒ
to apply the new setting.
Note
If the No Activity Tripped After setting (xx009) is set to 0
(not active) this setting will have no affect.
(Partitions-Alarms)
1
for on (alarm is
ƒ
to apply
(Partitions-Alarms)
1
for on (generate
ƒ
to apply the new setting.
(Partitions-Alarms)
0 for not active.
(Partitions-Alarms)
19