System Date
17001
(Default = 01 01 00 [1/1/00]) This setting lets you adjust the panel
calendar to the correct month, day, and year.
To set the System Date:
1.
Enter the item number.
2.
Enter the correct month (01–12), day (01–31), and year
(00–99). For example, enter 090100 for September 1,
2000.
ƒ . The display shows the new date.
3.
Press
System Time
17002
(Default = 12 00 00 [12:00:00])This setting lets you adjust the
panel clock to the correct time. The panel uses a 24-hour clock.
For example, to set the time to 4:17 PM, enter 1617.
To set the System Time:
Enter the item number. Enter the correct time (0000–2359). Press
ƒ
. The display shows the new time.
System Day of Week
17003
(Default = 5 [Saturday]) This setting lets you adjust the panel to
the current day of week.
Day Format
‰ 0—Monday
‰ 1—Tuesday
‰ 2—Wednesday
‰ 3—Thursday
‰ 4—Friday
‰ 5—Saturday
‰ 6—Sunday
To set the System Day of Week:
Enter the item number. Enter the day of week using the above
ƒ
format (0–6) and press
.
Time Format
17100
(Default = off) This setting allows you to choose whether the
panel time format is in 12- (AM and PM) or 24-hour format. If on,
the panel will announce and display the time in 24-hour format.
To turn Time Format On/Off:
Once the item number has been entered, enter
ƒ
off. Press
to apply the new setting.
Advent Commercial Fire System
Detect Receiver Failure
17078
(System)
(Default = on) When on, (and a wireless commercial transceiver
is installed), the panel will detect and indicate wireless receiver
failure.
To turn Detect Receiver Failure On/Off:
Once the item number has been entered, enter
off. Press
Panel Calls Back to Downloader
17122
(Default = off) Select whether or not to have the panel call back
the downloader when the downloader calls out to the panel with a
(System)
job.
To turn Panel Calls Back to Downloader On/Off:
Once the item number has been entered, enter
off. Press
Phone Off-Hook is Activity
17092
(Default = on) Select whether or not a phone off-hook condition is
considered an activity.
(System)
To turn Phone Off-Hook is Activity On/Off:
Once the item number has been entered, enter
off. Press
RF Supervisory Time A
RF Supervisory Time B
A; 17049, B: 17050
(Defaults = A: 4 hours, B: 24 hours) The RF Supervisory Time is
the time (in hours) in which the panel must receive a transmission
from a wireless zone. If the panel does not receive a transmission
within this time window, a trouble report occurs. Advent panels
have two RF Supervisory Times (A and B).
To set RF Supervisory Time:
(System)
Enter the desired item number. Enter the RF Supervisory Time in
hours (2–24). Press
1
0
for on, or
for
ƒ
to apply the new setting.
ƒ
to apply the new setting.
Note
For residential use only.
ƒ
to apply the new setting.
ƒ
to apply the new setting.
(System)
1
0
for on, or
for
(System)
1
0
for on, or
for
(System)
1
0
for on, or
for
(System)
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents