Delete Zones
47002
(Default = n/a) Use this item number to delete zones from panel
memory. You must delete zones one at a time.
Note
Deleting zones does not delete the zone text associated
with the deleted zone number. To delete zone text use
item number 49001, Zone Text.
To Delete Zones from panel memory:
1.
Once in program mode enter
shows ENTER ZONE NUMBER OR PRESS * TO CAN-
CEL.
2.
Enter the 3-digit zone number you wish to delete and
ƒ .
press
3.
The display shows ZONE nn DELETED.
4.
To delete another zone, repeat the above procedure.
Zone Text
49001
(Default = none) Use the following guidelines to "name" zones.
‰ Use the item numbers that appear in Table B.2 on page 92
for characters and words listed there.
‰ If a desired word does not appear in Table B.2, create it
using the characters (custom text).
‰ When using words from Table B.2, spaces between them
appear automatically. When using characters from Table
B.2 to create words, you must reserve an item number for
a 'space' after the word.
‰ Each character or word uses up one item number. For
example, a word from the list counts as one item number.
A created word (such as BOY'S) counts as six item num-
bers—4 letters, 1 apostrophe, and 1 space.
‰ Only 8 item numbers are allowed for each zone name, so
plan ahead before programming zone text. You may need
to abbreviate words to avoid running out of item numbers.
To program Zone Text:
1.
Once in program mode enter
shows ENTER ZONE NUMBER OR PRESS * TO CAN-
CEL.
2.
Enter the desired zone number and press
shows TEXT FOR ZONE n IS current zone text. ENTER
TEXT NUMBERS OR PRESS # TO ACCEPT.
3.
Enter the numbers of the desired characters or words. If
you make a mistake press
4.
Once all numbers have been entered, press
The display shows the new zone text.
To delete Zone Text:
1.
Once in program mode enter
shows ENTER ZONE NUMBER OR PRESS * TO CAN-
CEL.
2.
Enter the desired zone number and press
shows TEXT FOR ZONE n IS current zone text. ENTER
TEXT NUMBERS OR PRESS # TO ACCEPT.
000 and press ƒ . The display shows TEXT FOR
3.
Enter
ZONE n IS NO TEXT.
Advent Commercial Fire System
(Zones)
47002 . The display
(Zones)
49001 . The display
ƒ . The display
‚ to start over.
ƒ to accept.
49001 . The display
ƒ . The display
List Zones
47003
(Default = n/a) Use this item number to list information about
existing zones. The system will list the zone number, any zone
text, zone type number, and the partition/area number.
To List Zones:
47003
Once in program mode enter
ZONE nn, any zone text, TYPE nn, PARTITION/AREA n.
The panel will scroll through and display information about each
ƒ
zone. To skip forward press
lists all the zones it will return to the program menu.
(Zones)
. The display will show
. To exit press
. Once the panel