GE Advent Installation Instructions Manual page 24

Commercial fire system
Table of Contents

Advertisement

Print Partition/Area Events
xx091
(Default = on) If on, the panel will print partition/area events on a
local printer.
To Print Partition/Area Events:
Once the item number has been entered, enter
printing of partition/area events or
ƒ
partition/area events. Press
Delay Between Generated Panic Alarm and Alarm
Reporting
xx012
(Default = 05 seconds) This setting allows you to specify the
length of time (in seconds) between the time a panic alarm
condition is detected, and a panic report is sent to the central
station. This allows users time to cancel a false alarm.
Note
If Cancel Event Cancels Report setting (xx089) is set to
off, this setting will have no affect.
Specifying the Delay Between Generated Panic
Alarm and Alarm Reporting:
Once the item number has been entered, enter the number of
seconds (1–120) you wish the panel to wait before sending a
ƒ
panic report. Press
to apply the new setting.
Delay Between Generated Standard Alarm and Alarm
Reporting
xx013
(Default = 05 seconds) This setting allows you to specify the
length of time (in seconds) between the time a non-panic and non-
fire alarm condition is detected, and a report is sent to the central
station. This allows users time to cancel a false alarm.
Note
If Cancel Event Cancels Report setting (xx089) is set to
off, this setting will have no affect.
Specifying the Delay Between Generated Standard
Alarm and Alarm Reporting:
Once the item number has been entered, enter the number of
seconds (1–120) you wish the panel to wait before sending a
ƒ
report. Press
to apply the new setting.
22
(Partitions-Reporting)
1
(on) to enable
0
(off) to disable printing of
to apply the new setting.
(Partitions-Reporting)
(Partitions-Reporting)
Delay Between Generated Fire Alarm and Alarm
Reporting
xx014
(Default = 0 minutes) This setting allows you to specify the length
of time (in minutes) between the time a fire alarm condition is
detected, and a report is sent to the central station. This allows
users time to cancel a false alarm.
Note
If Cancel Event Cancels Report setting (xx089) is set to
off, this setting will have no affect.
Specifying the Delay Between Generated Fire
Alarm and Alarm Reporting:
Once the item number has been entered, enter the number of
minutes (0–15) you wish the panel to wait before sending a
ƒ
report. Press
to apply the new setting.
Second Fire Alarm Ends Reporting Delay
xx090
(Default = on) If on, and a fire report delay is in progress, a
second fire alarm condition will end the delay between generated
fire alarm and alarm reporting (xx014), immediately sending a
report to the central station.
Programming Second Fire Alarm Ends Reporting
Delay:
Once the item number has been entered, enter
setting on (second alarm ends delay) or
to apply the new setting.
Second Intrusion Causes Report
xx077
(Default = off) If on, the first trip of an intrusion zone causes a
local police alarm. A second trip (different intrusion zone) within
four minutes generates a report. If off, the first trip of an intrusion
zone generates both an alarm and report.
To set the Second Intrusion Causes Report:
Once the item number has been entered, enter
0
setting on or
to turn it off. Press
Generate Restoral Reports for Reporting Zone Types
xx112
(Default = off) If on, restoral reports are generated for all
reporting zone types (which require restoral). If off, the zone type
definition dictates whether on not a restoral report is generated.
To turn Generate Restoral Reports for Reporting
Zone Types On/Off:
Once the item number has been entered, enter
0
setting on or
to turn it off. Press
(Partitions-Reporting)
(Partitions-Reporting)
1
to turn the
0
ƒ
to turn it off. Press
(Partitions-Reporting)
1
to turn the
ƒ
to apply the new setting.
(Partitions-Reporting)
1
to turn the
ƒ
to apply the new setting.
Advent Commercial Fire System