Zone Attributes (Edit Zones)
47004
(Default = n/a) Use this item number to edit the following zone
attributes.
‰ 1—Critical Security Zone (Default = 0 [Off])
Enter 0 to turn attribute Off, 1 to turn attribute On. Critical
zones require special authority (partition master and full
authority codes) in order to be bypassed.
‰ 2—RF Supervisory Time (Default = A [4 hours])
Enter 0 for RF Supervisory Time A (17049), 1 for
Supervisory Time B (17050).
‰ 3—Zone Activity Threshold (Default = 0 [None])
Enter 0 for None, 1 for Threshold 1 (xx018), 2 for Thresh-
old 2 (xx019), 3 for Threshold 3 (xx020).
‰ 4—Hardwire Smoke Verify (Default = 0 [Off])
Enter 0 to turn attribute Off, 1 to turn attribute On. If on,
when a hardwire smoke detector is tripped, the panel will
remove power for 3 seconds to reset the smoke. If a sec-
ond trip occurs within 120 seconds, an alarm will sound
and a report will be sent to the central station.
‰ 5—Delayed Zone (Default = 0 Off)
Enter 0 to turn attribute Off, 1 to turn attribute On (see
17117).
‰ 6—Floor (Default = 0 [None])
Enter the floor number the zone resides on (1–90 above
ground, 91–99 below ground, 0 = None) (see item 17074
on page 46).
‰ 7—not supported
‰ 8—not supported
‰ 9—not supported
‰ 10—Warning message index (Default = 0 [None])
Enter the desired warning message (1–5). If learned into
zone type 70 it will play the desired warning message.
1 = Evacuation Message 1
2 = Evacuation Message 2
3 = Evacuation Message 3
4 = Evacuation Message 4
5 = Weather Warning Message
‰ 11—Zone Bypass Group (Default = 0 [None])
Enter the desired bypass group number (0–32). This will
allow users to directly bypass and unbypass groups of
zones.
To Edit Zone Attributes:
1.
Once in program mode enter
shows ENTER ZONE NUMBER OR PRESS * TO CAN-
CEL.
2.
Enter the desired zone number and press
shows ENTER ATTRIBUTE NUMBER OR PRESS * TO
CANCEL.
3.
Enter the attribute number from the list above and press
ƒ . The display will show the current attribute setting. If
desired, change the attribute setting.
ƒ to apply changes. To edit another attribute repeat
4.
Press
step 1.
38
(Zones)
47004 . The display
ƒ . The display
Test Buddies
47005
(Default = n/a) Use this item number to test zone buddies.
To Test Buddies:
47005
Once in program mode enter
BUDDY TEST MODE. Once the test is complete the display will
list buddies (see List Buddies 47006).
List Buddies
47006
(Default = n/a) Use this item number to list information about
existing buddy zones. The system will list the buddy zone
number, ID, and latest buddy test results.
To List Buddies:
47006
Once in program mode enter
four buddies.
‰ If the buddy doesn't exists, the panel will display BUDDY
n INVALID.
‰ If the buddy failed the latest test (47005), the panel will
display BUDDY n FAILED.
‰ If the buddy passed the latest test, the signal strength will
be displayed.
The panel will scroll through and display information about each
buddy. To skip forward press
lists all the buddies it will return to the program menu.
Zone Delay Time
17117
(Default = 10 seconds) Set the time delay (in seconds) between a
zone being tripped and the trip being processed by the panel. This
allows time for a zone to reset.
Note
This setting only applies to zones programmed as
delayed.
To set Zone Delay Time:
Enter the item number. Enter the delay time (1–250 seconds) and
ƒ
press
.
Smoke Loop Reset Time
17051
(Default = 3 seconds) Select the time (in seconds) for a zone to
reset.
To set Smoke Loop Reset Time:
Enter the item number. Enter the reset time (3-15 seconds) and
ƒ
press
.
(Zones)
. The display will show
(Zones)
. The display will list all
ƒ
. To exit press
. Once the panel
(Zones)
(Zones)
Advent Commercial Fire System