Battery Voltage Shutdown is Canceled
17040
(Default = 176 (10.4V)) This setting allows you to set the backup
battery voltage at which a system shutdown (during an AC power
failure) is canceled (set in 1/17 volt units).
To set Battery Voltage Shutdown is Canceled:
Once in program mode enter the item number. Enter the desired
voltage (168–184 [9.9–10.8V]) and press
AC Stable Time
17036
(Default = 8 seconds) This setting allows you to specify the time
(in seconds) that AC power must be lost or restored before a
trouble, or trouble restoral is generated. These events are not
reported immediately.
To set AC Report Delay:
Once in program mode enter the item number. Enter the desired
ƒ
time (0–200) and press
.
AC Frequency
17123
(Default = 0 [60 Hz]) This setting allows you to choose the AC
frequency that is powering the panel.
To set the AC Frequency:
Once in program mode enter the item number. Enter
0
(off), or
for 60 Hz (on). Press
Panel Latitude
17110
(Default = 0 degrees) This setting allows you to specify the
latitude (in degrees) where the panel is located. This information
is then used by the panel when automatically adjusting sunrise/
sunset schedules.
To set the Panel Latitude:
Once in program mode enter the item number. Enter the desired
ƒ
latitude (0–65) and press
.
On Premises Pager ID 1
On Premises Pager ID 2
1: 17060, 2: 17061
(Default = 0000000) This setting allows you to specify 7-digit
pager IDs that will identify the 2 different pager groups in a local
paging network.
To specify On Premises Pager IDs:
Once in program mode enter the item number. Enter the desired
7-digit (0–9) pager ID and press
48
(System)
ƒ
.
(System)
(System)
1
for 50 Hz
ƒ
to apply the new setting.
(System)
(System)
ƒ
.
Miscellaneous Settings
Downloader Account Number
17109
(Default = 00000000) The Downloader Account Number is used
to identify the panel to Advent Downloader.
To enter a Downloader Account Number:
1.
Once the desired item number has been entered the cur-
rent account number will be displayed.
2.
Enter an 8-digit number (0–9) and press
Reset Panel
50001
(Default = n/a) This setting allows you to clear any errors the
panel may have by "rebooting" the system. All settings will
remain unchanged.
To Reset the Panel:
1.
Enter the installer code. Enter
99 and then ƒ . Wait about a minute for the panel
2.
Press
to reset.
Software/Hardware Version
50003
(Default = n/a) This setting allows you to view and identify panel
hardware and software version.
To view System Version:
1.
Enter the installer code.
50003 . The panel displays SYSTEM ID
2.
Enter
nnnnnnnn VERSION n.nn nnn.nnn PANEL TYPE n
SNAPCARD n n.
Panel Type Formats
0—Commercial Burg.
1—Home Navigator
2—Commercial Fire
3—Home Navigator High
4—Commercial Burg. High
5—Commercial Fire High
6—not used
7—Commercial Burg. Low
8—Commercial Fire Low
SnapCard Type Formats
0—none
1—(not used)
2—NAC
3—8Z input
4—4 relay output
5—quad smoke loop
6—24V smoke loop
7—(not used)
8—4Z input, 2 relay output
(Customer)
ƒ .
50001 .
Advent Commercial Fire System