Specific Phone Number Settings - GE Advent Installation Instructions Manual

Commercial fire system
Table of Contents

Advertisement

System Account Number 1
System Account Number 2
1: 17102, 2: 17103
(Default = 00000000) Enter an 8-digit system account number
which will identify the panel to the central station when reporting
system events. System Account Number 1 is reported on
reporting phone 1 and its backup. System account number 2 is
reported on reporting phone 2 and its backup.
Account Number Format:
‰ for 0 enter 00
‰ for 1 enter 01
‰ for 2 enter 02
‰ for 3 enter 03
‰ for 4 enter 04
‰ for 5 enter 05
‰ for 6 enter 06
‰ for 7 enter 07
‰ for 8 enter 08
‰ for 9 enter 09
‰ for A enter 10
‰ for B enter 11
‰ for C enter 12
‰ for D enter 13
‰ for E enter 14
‰ for F enter 15
To enter a System Account Number
1.
Once the desired item number has been entered the cur-
rent system account number will be displayed.
Note
If a Dealer Access Code has been programmed, you will
be prompted to enter it.
2.
Enter the new system account number using the list
above. For example, if you wanted the system account
number to be "123456AB," at the keypad you would
enter "01, 02, 03, 04, 05, 06, 10, 11."
ƒ and the touchpad displays the new system
3.
Press
account number.
Note
System account numbers must equal 8 characters. If you
enter less than 8 characters the panel will automatically
replace the blank spaces with leading zeros (0).
Pager ID
17058
(Default = 00000) The Pager ID identifies the panel to pager-
holders. Select the ID to be sent with pager reports.
To set the Pager ID:
Once the item number has been entered, enter the 5-digit Pager ID
(00000–99999) to be sent with pager reports and press
Advent Commercial Fire System
Phone Test Interval
17034
(Phone)
(Default = 1 day [comm], 7 days [home nav]) Select the number
of days between automatic phone test reports to all enable central
station phone numbers. Entering 0 will disable automatic phone
test.
To set Phone Test Interval:
Once the item number has been entered, (17-034) enter the
number of days (0–255). Press

Specific Phone Number Settings

Specific phone number settings allow you to program cen-
tral monitoring station, downloader, and pager phone num-
bers.
Note
If a Dealer Access Code has been programmed, you will
be prompted to enter it when setting/changing specific
phone settings.
‰ Phone numbers 19–22 are central monitoring station
reporting phone numbers and function as follows:
19 = phone 1
20 = phone 1 backup
21 = phone 2
22 = phone 2 backup
‰ Phone numbers 23–24 are downloader phone numbers and
function as follows:
23 = downloader
24 = downloader backup
Note
Downloader phone numbers are for commercial burglary
panels only.
‰ Phone numbers 25–40 are reporting pager phone numbers
1 through 16.
Phone Number Enable
yy001
(Default = off) Select whether or not to enable the phone number.
If on, the panel will use the number when reporting or
downloading. If off, the number will be skipped.
To turn Phone Number Enable On/Off:
Once the item number has been entered (19001–24001), enter
to turn this setting on (call), or
to apply the new setting.
(Phone)
ƒ
.
(Phone)
ƒ
to apply the new setting.
(Phone)
0
to turn it off (no call). Press
1
ƒ
29