NOTE!
When P204 = 5 or 6, parameters P295 (Inv. Rated Current), P296 (Line Rated Voltage) and P308
(Serial Address) are not changed.
NOTE!
In order to upload the user parameters (P204 = 7), the factory default must be uploaded first
(P204 = 5 or 6).

5.3 SITUATIONS FOR CONFIG STATUS

The CONFIG status is indicated by the HMI "ConF" status, as well as in parameters P006 and P680. Such status
indicates that the CFW100 cannot enable the output PWM pulses because the inverter configuration is incorrect
or incomplete. For further details about indications of CONFIG state on the HMI, refer to
PARAMETERS on page 14-1.
The table below shows the situations of CONFIG status, where the user can identify the origin condition through
parameter P047.
P047
0
Out of CONFIG status. The HMI and parameters P006 and P680 must not indicate ConF.
1
Two or more DIx (P263...P270) programmed for (4 = Forward Run).
2
Two or more DIx (P263...P270) programmed for (5 = Reverse Run).
3
Two or more DIx (P263...P270) programmed for (6 = Start).
4
Two or more DIx (P263...P270) programmed for (7 = Stop).
5
Two or more DIx (P263...P270) programmed for (8 = Direction of Rotation).
6
Two or more DIx (P263...P270) programmed for (9 = LOC/REM).
7
Two or more DIx (P263...P270) programmed for (11 = Accelerate E.P.)
8
Two or more DIx (P263...P270) programmed for (12 = Decelerate E.P.)
9
Two or more DIx (P263...P270) programmed for (14 = 2
10
Reserved.
11
Two or more DIx (P263...P270) programmed for (24 = Disable Flying Start).
12
Two or more DIx (P263...P270) programmed for (26 = Programming Off).
13
Reserved.
14
Reserved.
15
DIx (P263...P270) programmed for (4 = Forward Run) without DIx (P263...P270) programmed for (5 = Reverse Run) or the
opposite.
16
DIx (P263...P270) programmed for (6 = Start) without DIx (P263...P270) programmed for (7 = Stop) or the opposite.
17
P221 or P222 programmed for (8 = Multispeed) without DIx (P263...P270) programmed for (13 = Multispeed) or the opposite.
18
P221 or P222 programmed for (7 = E.P.) without DIx (P263...P270) programmed for (11 = Accelerate E.P) or the opposite.
P224 programmed for (1 = DIx) OR P227 programmed for (1 = DIx) without DIx (P263...P270) programmed for (1 = Run/Stop)
19
AND without DIx (P263...P270) programmed for (2 = General Enable) AND without DIx (P263...P270) programmed
for (3 = Quick Stop) AND without DIx (P263...P270) programmed for (4 = Forward Run) AND without DIx (P263...P270)
programmed for (6 = Start).
20
Serial baud rate configured for 38400 bps (P310 = 2) and use of the control mode VVW (P202 = 5).
21
P221 or P222 programmed for (8 = Multispeed) with DI1 (P263) AND DI2 (P264) OR DI1 (P263) AND DI5 (P267) OR
DI1 (P263) AND DI6 (P268) OR DI2 (P264) AND DI5 (P267) OR DI2 (P264) AND (P268) OR DI5 (P267) AND DI6 (P268)
programmed for (13 = Multispeed).
22
Minimum Frequency Reference (P133) greater than Maximum Frequency Reference (P134).
Table 5.3: Situations for CONFIG status