Download Print this page
WEG CFW100 Series Quick Reference

WEG CFW100 Series Quick Reference

V3.1x parameters, alarms and faults
Hide thumbs Also See for CFW100 Series:

Advertisement

Available languages

Available languages

Quick Links

Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
Convertidor de Frecuencia
Inversor de Frequência
CFW100 V3.1X
Quick Reference of Parameters, Alarms and Faults
Referencia Rápida de los Parámetros, Alarmas y Fallas
Referência Rápida dos Parâmetros, Alarmes e Falhas

Advertisement

loading

Summary of Contents for WEG CFW100 Series

  • Page 1 Motors | Automation | Energy | Transmission & Distribution | Coatings Frequency Inverter Convertidor de Frecuencia Inversor de Frequência CFW100 V3.1X Quick Reference of Parameters, Alarms and Faults Referencia Rápida de los Parámetros, Alarmas y Fallas Referência Rápida dos Parâmetros, Alarmes e Falhas...
  • Page 3 Quick Reference of Parameters, Alarms and Faults Series: CFW100 Language: English Document: 10006259370 / 01 Software version: 3.1X Build 1180 Publication Date: 04/2019...
  • Page 4 SUMMARY OF REVISIONS Version Revision Description 3.0X First edition. 3.1X General Revision.
  • Page 5 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P000 Access to Parameters 0 to 9999 P001 Speed Reference 0 to 9999 P002 Output Speed (Motor) 0 to 9999 P003 Motor Current 0.0 to 10.0 A P004 DC Link Voltage 0 to 524 V...
  • Page 6 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P082 Third Fault on Fire Mode 0 to 999 P100 Acceleration Time 0.1 to 999.9 s 5.0 s P101 Deceleration Time 0.1 to 999.9 s 10.0 s P102 Acceleration Time 2nd Ramp 0.1 to 999.9 s...
  • Page 7 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P202 Type of Control 0 = V/f 1 = Quadratic V/f 2 to 4 = Not Used 5 = VVW P204 Load/Save Parameters 0 to 4 = Not Used 5 = Load 60 Hz 6 = Load 50 Hz 7 = Load User...
  • Page 8 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P225 LOC JOG Selection 0 = Disabled 1 = Not Used 2 = DIx 3 = Serial/USB 4 = Not Used 5 = CO/DN 6 = SoftPLC P226 REM FWD/REV Selection See options in P223...
  • Page 9 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P251 AO1 Output Function 0 = Speed Ref. 1 = Not Used 2 = Real Speed 3 to 4 = Not Used 5 = Output Current 6 = Not Used 7 = Active Current 8 to 10 = Not Used...
  • Page 10 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P264 DI2 Input Function 0 = Not Used 1 = Run/Stop 2 = General Enable 3 = Quick Stop 4 = Foward Run 5 = Reverse Run 6 = Start 7 = Stop 8 = Direction of Rotation...
  • Page 11 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P265 DI3 Input Function 0 = Not Used 1 = Run/Stop 2 = General Enable 3 = Quick Stop 4 = Foward Run 5 = Reverse Run 6 = Start 7 = Stop 8 = Direction of Rotation...
  • Page 12 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P266 DI4 Input Function 0 = Not Used 1 = Run/Stop 2 = General Enable 3 = Quick Stop 4 = Foward Run 5 = Reverse Run 6 = Start 7 = Stop 8 = Direction of Rotation...
  • Page 13 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P275 DO1 Function 0 = Not Used 1 = F* ≥ Fx 2 = F ≥ Fx 3 = F ≤ Fx 4 = F = F* 5 = Not Used 6 = Is >Ix 7 = Is <Ix...
  • Page 14 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P312 Serial Protocol 0 to 1 = Reserved 2 = Modbus RTU Slave 3 to 4 = Reserved 5 = ModBus RTU Master P313 Action for Communic. Error 0 = Inactive 1 = Ramp Stop 2 = General Disable...
  • Page 15 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P680 Logical Status 0 to FFFF (hexa) Bit 0 = Reserved Bit 1 = Run Command Bit 2 = Fire Mode Bit 3 to 4 = Reserved Bit 5 = 2nd Ramp Bit 6 = Config.
  • Page 16 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P705 CAN Controller Status 0 = Disabled 1 = Auto-baud 2 = CAN Active 3 = Warning 4 = Error Passive 5 = Bus Off 6 = No Bus Power P706 RX CAN Telegrams 0 to 9999...
  • Page 17 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Param. Description Adjustable Range Factory Setting Prop. P914 SoftPLC Parameter 5 -9999 to 9999 P915 SoftPLC Parameter 6 -9999 to 9999 P916 SoftPLC Parameter 7 -9999 to 9999 P917 SoftPLC Parameter 8 -9999 to 9999 P918 SoftPLC Parameter 9 -9999 to 9999...
  • Page 18 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS SoftPLC Parameter Configuration for PID Controller Application (P903 = 1) Param. Description Adjustable Range Factory Setting Prop. P919 PID Controller Logical Status 0 to FFFF (hexa) Bit 0 = Sleep Mode Active (A750) Bit 1 = PID in Manual (0) / Automatic (1) Bit 2 = PV Low Level (A760) Bit 3 = PV Low Level (F761)
  • Page 19 Table 1.3 on page High ambient temperature around the inverter and high output current. For further information, refer to of the user’s manual available for download on the website: www.weg.net. Blocked or defective fan. Heatsink is too dirty, preventing the air flow. F051 Overtemperature fault measured on the High temperature at IGBTs.
  • Page 20 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Fault / Alarm Description Possible Causes F082 Fault in data transfer using MMF Attempt to download data from the flash memory module to Fault in Data Transfer (MMF) accessory. the inverter with the inverter energized. Attempt to download a SoftPLC application incompatible with the destination inverter.
  • Page 21 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Fault / Alarm Description Possible Causes F233 It indicates that the CAN interface has Measure if there is voltage within the allowed range between No Power Supply on the CAN no power supply between pins V(-) and pins V(-) and V(+) of the CAN interface connector.
  • Page 22 QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS Fault / Alarm Description Possible Causes F750/A750 to Fault/Alarm range intended for the Defined by the user’s application developed in the SoftPLC F799/A799 user’s application developed in the function. User’s Faults/Alarms for SoftPLC function. SoftPLC 22 | CFW100...
  • Page 23 APPENDIX APPENDIX - TECHNICAL SPECIFICATIONS Table 1.1: Situations for CONFIG status P047 Condition Out of CONFIG status. The HMI and parameters P006 and P680 must not indicate ConF Two or more DIx (P263...P270) programmed for (4 = Forward Run) Two or more DIx (P263...P270) programmed for (5 = Reverse Run) Two or more DIx (P263...P270) programmed for (6 = Start) Two or more DIx (P263...P270) programmed for (7 = Stop) Two or more DIx (P263...P270) programmed for (8 = Direction of Rotation)
  • Page 24 Referencia Rápida de los Parámetros, Alarmas y Fallas Serie: CFW100 Idioma: Español Documento: 10006259370 / 01 Versión del software: 3.1X Build 1180 Fecha de la Publicación: 04/2019...
  • Page 25 SUMARIO DE LAS REVISIONES Versión Revisión Descripción 3.0X Primera edición. 3.1X Revisión General. CFW100 | 25...
  • Page 26 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P000 Acceso Parámetro 0 a 9999 P001 Referencia Velocidad 0 a 9999 P002 Velocidad de Salida (Motor) 0 a 9999 P003 Corriente Motor 0,0 a 10,0 A P004 Tensión Link DC...
  • Page 27 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P082 Tercera Falla en Fire Mode 0 a 999 P100 Tiempo Aceleración 0,1 a 999,9 s 5,0 s P101 Tiempo Desaceleración 0,1 a 999,9 s 10,0 s P102 Tiempo Aceler.
  • Page 28 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P202 Tipo de Control 0 = V/f 1 = V/f Cuadrático 2 a 4 = Sin Función 5 = VVW P204 Carga/Salva Parám. 0 a 4 = Sin Función 5 = Carga 60 Hz 6 = Carga 50 Hz...
  • Page 29 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P225 Selección JOG LOC 0 = Inactivo 1 = Sin Función 2 = DIx 3 = Serial/USB 4 = Sin Función 5 = CO/DN 6 = SoftPLC P226 Selección Giro REM...
  • Page 30 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P251 Función Salida AO1 0 = Ref. Velocidad 1 = Sin Función 2 = Velocidad Real 3 a 4 = Sin Función 5 = Corr. Salida 6 = Sin Función 7 = Corr.
  • Page 31 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P263 Función Entrada DI1 0 = Sin Función 1 = Gira/Para 2 = Hab. General 3 = Parada Rápida 4 = Avance 5 = Retroceso 6 = Start 7 = Stop 8 = Sentido Giro...
  • Page 32 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P264 Función Entrada DI2 0 = Sin Función 1 = Gira/Para 2 = Hab. General 3 = Parada Rápida 4 = Avance 5 = Retroceso 6 = Start 7 = Stop 8 = Sentido Giro...
  • Page 33 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P265 Función Entrada DI3 0 = Sin Función 1 = Gira/Para 2 = Hab. General 3 = Parada Rápida 4 = Avance 5 = Retroceso 6 = Start 7 = Stop 8 = Sentido Giro...
  • Page 34 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P266 Función Entrada DI4 0 = Sin Función 1 = Gira/Para 2 = Hab. General 3 = Parada Rápida 4 = Avance 5 = Retroceso 6 = Start 7 = Stop 8 = Sentido Giro...
  • Page 35 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P275 Función de la Salida DO1 0 = Sin Función 1 = F* ≥ Fx 2 = F ≥ Fx 3 = F ≤ Fx 4 = F = F* 5 = Sin Función 6 = Is >Ix...
  • Page 36 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P312 Protocolo Serial 0 a 1 = Reservado 2 = Modbus RTU Esclavo 3 a 4 = Reservado 5 = ModBus RTU Maestro P313 Acción p/ Erro Comunic 0 = Inactivo...
  • Page 37 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P680 Estado Lógico 0 a FFFF (hexa) Bit 0 = Reservado Bit 1 = Comando Gira Bit 2 = Fire Mode Bit 3 a 4 = Reservado Bit 5 = 2ª...
  • Page 38 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P705 Estado ControladorCAN 0 = Inactivo 1 = Auto-baud 2 = CAN Activo 3 = Warning 4 = Error Passive 5 = Bus Off 6 = No Alimentado P706 Telegramas CAN RX...
  • Page 39 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P914 Parámetro SoftPLC 5 -9999 a 9999 P915 Parámetro SoftPLC 6 -9999 a 9999 P916 Parámetro SoftPLC 7 -9999 a 9999 P917 Parámetro SoftPLC 8 -9999 a 9999 P918 Parámetro SoftPLC 9...
  • Page 40 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Configuración de los Parámetros de la SoftPLC para Aplicación Controlador PID (P903 = 1) Parám. Descripción Rango de Valores Ajuste de Fábrica Prop. P919 Estado Lógico del Controlador PID 0 a FFFF (hexa) Bit 0 = Modo Dormir Activo (A750) Bit 1 = PID en Manual (0) / Automático (1) Bit 2 = Nivel Bajo de la VP (A760)
  • Page 41 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS cfg = Parámetro de configuración, solamente puede ser alterado con el motor parado V/f = Parámetro disponible en modo V/f VVW = Parámetro disponible en modo VVW CFW100 | 41...
  • Page 42 Temperatura ambiente al rededor del convertidor alta y corriente de salida elevada. Para más informaciones consulte el manual del usuario, disponible para download en el sitio: www.weg.net. Ventilador bloqueado o defectuoso. Disipador muy sucio, impidiendo o flujo de aire. F051 Falla de sobretemperatura medida en Temperatura alta en los IGBTs.
  • Page 43 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Falla / Alarma Descripción Causas Probables F082 Falla en la transferencia de datos Intento de descargar los datos del módulo de memoria flash Falla en la Función Copy usando accesorio MMF. al convertidor, con éste energizado. Intento de descargar una aplicación SoftPLC incompatible con el convertidor de destino.
  • Page 44 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Falla / Alarma Descripción Causas Probables F228 Indica que el equipamiento paró de Verificar instalación de la red, cable roto o falla/mal contacto Timeout Comun. Serial recibir telegramas válidos, por un en las conexiones con la red, puesta a tierra. período mayor al programado en el Garantizar que el maestro envíe telegramas hacia el P314.
  • Page 45 REFERENCIA RÁPIDA DE LOS PARÁMETROS, ALARMAS Y FALLAS Falla / Alarma Descripción Causas Probables F709 La aplicación de la SoftPLC no está La aplicación de la SoftPLC está parada (P901 = 0 y P900 Aplicativo de la SoftPLC no se rodando.
  • Page 46 ANEXO ANEXO - ESPECIFICACIONES TÉCNICAS Tabla 1.1: Situaciones para el estado CONFIG P047 Condición Fuera del estado CONFIG. la HMI y los parámetros P006 y P680 no deben indicar ConF Dos o más DIx (P263...P270) programadas para (4 = Avance) Dos o más DIx (P263...P270) programadas para (5 = Retorno) Dos o más DIx (P263...P270) programadas para (6 = Start) Dos o más DIx (P263...P270) programadas para (7 = Stop)
  • Page 47 Referência Rápida dos Parâmetros, Alarmes e Falhas Série: CFW100 Idioma: Português Documento: 10006259370 / 01 Versão de software: 3.1X Build 1180 Data de publicação: 04/2019...
  • Page 48 SUMÁRIO DAS REVISÕES Versão Revisão Descrição 3.0X Primeira edição. 3.1X Revisão geral. 48 | CFW100...
  • Page 49 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P000 Acesso aos Parâmetros 0 a 9999 P001 Referência Velocidade 0 a 9999 P002 Velocidade de Saída (Motor) 0 a 9999 P003 Corrente do Motor 0,0 a 10,0 A P004 Tensão Link DC (Ud)
  • Page 50 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P082 Terceira Falha em Fire Mode 0 a 999 P100 Tempo Aceleração 0,1 a 999,9 s 5,0 s P101 Tempo Desaceleração 0,1 a 999,9 s 10,0 s P102 Tempo Acel.
  • Page 51 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P202 Tipo de Controle 0 = V/f 1 = V/f Quadrático 2 a 4 = Sem Função 5 = VVW P204 Carrega/Salva Parâm. 0 a 4 = Sem Função 5 = Carrega 60 Hz 6 = Carrega 50 Hz 7 = Carr.
  • Page 52 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P225 Seleção JOG LOC 0 = Inativo 1 = Sem Função 2 = DIx 3 = Serial/USB 4 = Sem Função 5 = CO/DN 6 = SoftPLC P226 Seleção Giro REM...
  • Page 53 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P251 Função da Saída AO1 0 = Ref. Veloc. 1 = Sem Função 2 = Veloc. Real 3 a 4 = Sem Função 5 = Corrente Saída 6 = Sem Função 7 = Corrente Ativa 8 a 10 = Sem Função...
  • Page 54 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P263 Função da Entrada DI1 0 = Sem Função 1 = Gira/Para 2 = Habilita Geral 3 = Parada Rápida 4 = Avanço 5 = Retorno 6 = Start 7 = Stop 8 = Sentido Giro...
  • Page 55 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P264 Função da Entrada DI2 0 = Sem Função 1 = Gira/Para 2 = Habilita Geral 3 = Parada Rápida 4 = Avanço 5 = Retorno 6 = Start 7 = Stop 8 = Sentido Giro...
  • Page 56 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P265 Função da Entrada DI3 0 = Sem Função 1 = Gira/Para 2 = Habilita Geral 3 = Parada Rápida 4 = Avanço 5 = Retorno 6 = Start 7 = Stop 8 = Sentido Giro...
  • Page 57 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P266 Função da Entrada DI4 0 = Sem Função 1 = Gira/Para 2 = Habilita Geral 3 = Parada Rápida 4 = Avanço 5 = Retorno 6 = Start 7 = Stop 8 = Sentido Giro...
  • Page 58 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P275 Função da Saída DO1 0 = Sem Função 1 = F* ≥ Fx 2 = F ≥ Fx 3 = F ≤ Fx 4 = F = F* 5 = Sem Função 6 = Is >...
  • Page 59 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P312 Protocolo Serial 0 a 1 = Reservado 2 = Modbus RTU Escravo 3 a 4 = Reservado 5 = ModBus RTU Mestre P313 Ação p/ Erro Comunic.
  • Page 60 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P680 Estado Lógico 0 a FFFF (hexa) Bit 0 = Reservado Bit 1 = Comando Gira Bit 2 = Fire Mode Bit 3 a 4 = Reservado Bit 5 = 2ª...
  • Page 61 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P705 Estado ControladorCAN 0 = Inativo 1 = Auto-baud 2 = CAN Ativo 3 = Warning 4 = Error Passive 5 = Bus Off 6 = Não Alimentado P706 Telegramas CAN RX...
  • Page 62 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P915 Parâmetro SoftPLC 6 -9999 a 9999 P916 Parâmetro SoftPLC 7 -9999 a 9999 P917 Parâmetro SoftPLC 8 -9999 a 9999 P918 Parâmetro SoftPLC 9 -9999 a 9999 P919 Parâmetro SoftPLC 10...
  • Page 63 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Configuração dos Parâmetros da SoftPLC para Aplicação Controlador PID (P903 = 1) Parâm. Descrição Faixa de Valores Ajuste de Fábrica Propr. P919 Estado Lógico do Controlador PID 0 a FFFF (hexa) Bit 0 = Modo Dormir Ativo (A750) Bit 1 = PID em Manual (0) / Automático (1) Bit 2 = Nível Baixo da VP (A760) Bit 3 = Nível Baixo da VP (F761)
  • Page 64 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS ro = Parâmetro somente leitura V/f = Parâmetro disponível em modo V/f cfg = Parâmetro de configuração, somente pode ser alterado com o motor parado VVW = Parâmetro disponível em modo VVW 64 | CFW100...
  • Page 65 Temperatura ambiente ao redor do inversor alta e corrente de saída elevada. Para mais informações consulte o manual do usuário, disponível para download no site: www.weg.net. Ventilador bloqueado ou defeituoso. Dissipador muito sujo, impedindo o fluxo de ar. F051 Falha de sobretemperatura medida Temperatura nos IGBTs alta.
  • Page 66 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Falha / Alarme Descrição Causas Prováveis F081 Falha de término de memória para Tentativa de salvar (P204 = 9) mais do que 32 parâmetros Término da Memória do salvar tabela parâmetros (com valores diferentes do padrão de fábrica) na tabela de Usuário usuário.
  • Page 67 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Falha / Alarme Descrição Causas Prováveis A211 Indica ao usuário que o inversor de Entrada digital programada para ativar Fire Mode está ativa. Inversor de frequência em Fire frequência está funcionando em Fire Mode Mode.
  • Page 68 REFERÊNCIA RÁPIDA DOS PARÂMETROS, ALARMES E FALHAS Falha / Alarme Descrição Causas Prováveis F709 Aplicativo SoftPLC não está Aplicativo da SoftPLC está parado (P901 = 0 e P900 = 3). Aplicativo da SoftPLC não está rodando. Estado da SoftPLC apresenta aplicativo incompatível com a rodando versão de firmware do inversor de frequência.
  • Page 69 ANEXO ANEXO - ESPECIFICAÇÕES TÉCNICAS Tabela 1.1: Situações para o estado CONFIG P047 Condição Fora do estado CONFIG. A HMI e os parâmetros P006 e P680 não devem indicar ConF Duas ou mais DIx (P263...P270) programadas para (4 = Avanço) Duas ou mais DIx (P263...P270) programadas para (5 = Retorno) Duas ou mais DIx (P263...P270) programadas para (6 = Liga) Duas ou mais DIx (P263...P270) programadas para (7 = Desliga)
  • Page 70 WEG Drives & Controls - Automação LTDA. Jaraguá do Sul – SC – Brazil Phone 55 (47) 3276-4000 – Fax 55 (47) 3276-4020 São Paulo – SP – Brazil Phone 55 (11) 5053-2300 – Fax 55 (11) 5052-4212 automacao@weg.net www.weg.net...