WEG CFW100 Programming Manual page 85

V2.4x
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

P014 – Value of Analog Output AO1
Adjustable
0.0 to 100.0%
Range:
Properties:
ro
Description:
This read-only parameters indicates the value of analog output AO1 in percentage of the full scale. The indicated
values is obtained after multiplication by the gain. Check the description of the parameters P251 to P253.
P251 – AO1 Output Function
Adjustable
0 = Speed Ref.
Range:
1 = Not used
2 = Effective Speed
3 = Not used
4 = Not used
5 = Output Current
6 = Not used
7 = Active Current
8 = Not used
9 = Not used
10 = Not used
11 = Motor Torque
12 = SoftPLC
13 to 20 = Not used
21 = Function 1 Application
22 = Function 2 Application
23 = Function 3 Application
24 = Function 4 Application
25 = Function 5 Application
26 = Function 6 Application
27 = Function 7 Application
28 = Function 8 Application
Properties:
cfg
Description:
This parameter sets the function of the analog output, according to function and scale presented in
on page
12-5.
Function
0
Speed reference at the input of the ramp P001
2
Effective Speed at the inverter output
5
Total Output Current RMS
7
Active Current
11
Torque on the Motor in relation to the rated torque
12
SoftPLC scale for analog output
16
Ixt overload of the motor (P037)
Digital and Analog Inputs and Outputs
Table 12.3: Full scale of the analog output
Description
Return
Advance
Factory
Setting:
Factory
2 = Effective
Setting:
Speed
Table 12.3
Full Scale
P134
P134
2xP295
2xP295
200.0 %
16383
100 %
CFW100 | 12-5