Logical Command and Speed Reference
Description:
The inverter status word is unique for all the sources and can only be accessed for reading. It indicates all the
relevant operating status and modes of the inverter. The function of each bit of P680 is described in
on page 7-12.
BIT
Function
0 to 4
Reserved
5
2
nd
6
Config. Status
7
Alarm
8
Running
9
Enabled
10
Forward
11
JOG
12
Remote
7
13
Undervoltage
14
Reserved
15
Fault
P682 – Serial / USB Control
Adjustable
Range:
Properties:
Description:
The inverter control word for a certain source is accessible for reading and writing, but read only access is
permitted for the other sources. The inverter has a common word for interface, which is defined by the function
of its bits separately as per
BIT
Function
0
Ramp Enable
1
General Enable
2
Run Forward
3
Enable JOG
4
Remote
5
2
nd
6
Reserved
7
Fault Reset
8 to 15
Reserved
7-12 | CFW100
-
0: 1
Acceleration and deceleration ramp by P100 and P101.
st
Ramp
1: 2
Acceleration and deceleration ramp by P102 and P103.
nd
0: Inverter operating in normal conditions.
1: Inverter in configuration state. It indicates a special condition in which the inverter cannot be
enabled, because it has parameterization incompatibility.
0: Inverter is not in alarm state.
1: Inverter is in alarm state.
0: Motor is stopped.
1: Inverter is running according to reference and command.
0: Inverter is completely disabled.
1: Inverter is completely enabled and ready to turn the motor.
0: Motor spinning reverse.
1: Motor spinning forward.
0: JOG function inactive.
1: JOG function active.
0: Inverter in Local mode.
1: Inverter in Remote mode.
0: No Undervoltage.
1: With Undervoltage.
-
0: Inverter is not in Fault state.
1: Some fault registered by the inverter.
0000h to FFFFh
ro
Table 7.5 on page
0: Stops the motor by deceleration ramp.
1: Spins the motor according to the acceleration ramp until reaching the speed reference value.
0: Disables the inverter completely, interrupting the power supply to the motor.
1: Enables the inverter completely, allowing the operation of the motor.
0: Spins the motor in the opposite direction of the reference signal (reverse).
1: Spins the motor in the direction of the reference signal (forward).
0: Disable JOG function.
1: Enable JOG function.
0: Inverter goes into Local mode.
1: Inverter goes into Remote mode.
0: Acceleration and deceleration ramp by P100 and P101.
Ramp
1: Acceleration and deceleration ramp by P102 and P103.
-
0: No function.
1: If in fault state, reset the fault.
-
Table 7.4: Status word
Description
7-12. The value of P682 is indicated in hexadecimal.
Table 7.5: Control word
Description
Return
Advance
Table 7.4