P271 – Digital Input Signal
Adjustable
0 = All DIx are NPN
Range:
1 = Reserved
2 = (DI5...DI8) - PNP
3 = Reserved
Properties:
cfg
Description:
It configures the default for the digital input signal, that is, NPN and the digital input is activated with 0 V, PNP
and the digital input is activated with +24 V.
a) RUN/STOP
It enables or disables the motor rotation through the acceleration and deceleration ramp.
b) GENERAL ENABLE
It enables the motor rotation through the acceleration ramp and disables it by cutting off the pulses immediately;
the motor stops by inertia.
c) QUICK STOP
When inactive, it disables the inverter by the emergency deceleration (P107).
Acceleration
ramp
Output
frequency
Active
DIx
Inactive
Figure 12.5: Example of the Run/Stop function
Acceleration ramp
Output
frequency
Active
DIx
Inactive
Figure 12.6: Example of the General Enable function
Acceleration
ramp
Output
frequency
Active
DIx
Inactive
Figure 12.7: Example of the Quick Stop function
Return
Advance
Digital and Analog Inputs and Outputs
Deceleration
ramp
Time
Time
Motor runs free
Time
Time
P107 -
Deceleration
ramp
Time
Time
Factory
0 = All DIx
Setting:
are NPN
CFW100 | 12-11