Logical Command and Speed Reference
P220 – Local/Remote Selection
Adjustable
Range:
Properties:
Description:
It defines the command origin source which will select between Local situation and Remote situation, where:
LOC: means Local situation default.
REM: means Remote situation default.
DIx: according to function programmed for digital input in P263 to P266.
7
CO / DN: CANopen or DeviceNet or Profibus DP Interface.
P221 – Frequency Reference Selection – LOCAL Situation
P222 – Frequency Reference Selection – REMOTE Situation
Adjustable
Range:
Properties:
Description:
These parameters define the origin source for the frequency reference in the Local situation and Remote situation.
Some comments on the options of this parameter:
AI1: it refers to the analog input signal according to
HMI: the reference value set by the keys and are contained in parametere P121.
E.P.: electronic potentiometer; refer to
7-4 | CFW100
0 = Always Local
1 = Always Remote
2 to 3 = Not Used
4 = Digital Input (DIx)
5 = Serial/USB (LOC)
6 = Serial/USB (REM)
7 to 8 = Not Used
9 = CO/DN (LOC)
10 = CO/DN (REM)
11 = SoftPLC
cfg
0 = HMI
1 = AI1
2 to 3 = Not Used
4 = Frequency Input (FI)
5 to 6 = Not Used
7 = E.P.
8 = Multispeed
9 = Serial/USB
10 = Not Used
11 = CO/DN
12 = SoftPLC
13 = Not Used
14 = AI1 > 0
15 to 16 = Not Used
17 = FI > 0
cfg
section 12.5 DIGITAL INPUT on page 12-8.
section 12.1 ANALOG INPUTS on page 12-1.
Return
Advance
Factory
0
Setting:
Factory
P221 = 0
Setting:
P222 = 2