WEG CFW100 Programming Manual page 72

V2.4x
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

Functions Common to All the Control Modes
P103 – Deceleration Time 2
Adjustable
Range:
Properties:
Description:
Deceleration time from maximum speed (P134) to zero when the 2
P106 – Emergency Ramp Acceleration Time
Adjustable
Range:
Properties:
Description:
Acceleration time from zero to maximum frequency (P134) when the Emergency Ramp is active.
P107 – Emergency Ramp Deceleration Time
Adjustable
Range:
Properties:
Description:
Deceleration time from maximum frequency (P134) to zero when the Emergency Ramp is active.
P104 – S Ramp
Adjustable
Range:
Properties:
Description:
This parameter allows the inverter acceleration and deceleration ramps to have a non-linear profile, similar to an
11
"S", aiming at reducing the mechanical shocks on the load, as shown in
11-2 | CFW100
Ramp
nd
0.1 to 999.9 s
0.1 to 999.9 s
0.1 to 999.9 s
0 = Inactive
1 = Active
cfg
Output
frequency
Acceleration time
(P100/P102)
Figure 11.1: S or Linear ramp
Ramp is active.
nd
Figure 11.1 on page
Linear ramp
Ramp S
Deceleration time
(P101/P103)
Return
Advance
Factory
10.0 s
Setting:
Factory
5.0 s
Setting:
Factory
5.0 s
Setting:
Factory
0
Setting:
11-2.
t (s)