WEG CFW100 Programming Manual page 98

V2.4x
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

Digital and Analog Inputs and Outputs
Value
Function
0
Not used
1
2
3
4
5
Not used
6
7
8 to 9
Not used
10
11
12
13
Without fault
14
Without F070
15
Not used
16
Without F021/F022
17
Not used
18
Without F072
19
4-20 mA OK
20
Not used
21
22 to 23
Not used
24
Ride-Through
25
Pre-Charge OK
26
With Fault
27
Not used
28
29 to 34
Not used
35
Without Alarm
Without Fault and
36
37
Function 1
38
Function 2
39
Function 3
40
Function 4
41
Function 5
42
Function 6
43
Function 7
44
Function 8
P281 – Fx Frequency
12
P282 – Fx Hysteresis
Adjustable
Range:
Properties:
Description:
These parameters set the hysteresis and actuation level on the Fx output frequency signal and on the F* ramp
input of the relay digital output. In this way, the relay commutation levels are "P281 + P282" and "P281 - P282".
12-18 | CFW100
Table 12.7: Digital Output Functions
It deactivates the digital output.
F* ≥ Fx
Active when the frequency reference F* (P001) is greater than Fx (P281).
F ≥ Fx
Active when the Output Frequency F (P002) is greater than Fx (P281).
F ≤ Fx
Active when the Output Frequency F (P002) is smaller than Fx (P281).
F = F*
Active if the Output Frequency F (P002) is equal to the reference F* (P001) (ramp end).
It deactivates the digital output.
Is > Ix
Active if the output current Is (P003) > Ix (P290).
Is < Ix
Active if the output current Is (P003) < Ix (P290).
It deactivates the digital output.
Remote
Active if the command is in the remote situation (REM).
Run
Active if the motor is running (active output PWM pulses).
Ready
Active if the inverter is ready for enabling.
Active if the inverter has no faults.
Active if the inverter has no overcurrent fault (F070).
It deactivates the digital output.
Active if the inverter has no overvoltage or undervoltage fault (F022 or F021).
It deactivates the digital output.
Active if the inverter has no motor overload fault (F072).
Active if AIx setting is 4 to 20 mA (P233 = 1 or 3) and AIx < 2 mA.
It deactivates the digital output.
Forward
Active if the inverter direction of rotation is forward.
It deactivates the digital output.
Active if the inverter is executing the Ride-Through function.
Active if the pre-charge relay of the DC link capacitors was already activated.
Active if the inverter has a fault.
It deactivates the digital output.
SoftPLC
It activates the output DOx according to the SoftPLC memory area. Check the SoftPLC user manual.
It deactivates the digital output.
Active when the inverter has no alarms.
Active when the inverter has neither alarms nor faults.
Alarm
-
-
-
-
-
-
-
-
0.0 to 300.0 Hz
Description
Return
Advance
Factory
P281 = 3.0 Hz
Setting:
P282 = 0.5 Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents