11.5 AVOIDED FREQUENCY

This inverter function prevents the motor from operating permanently at frequency values in which, for example,
the mechanical system goes into resonance (causing excessive vibration or noises).
P303 – Skip Frequency 1
Adjustable
Range:
P304 – Skip Frequency 2
Adjustable
Range:
P306 – Skip Band
Adjustable
Range:
Properties:
Description:
The actuation of those parameters is done as presented in
The passage by the avoided frequency band (2xP306) is done through acceleration/deceleration ramp.
The function does not operate correctly if two bands of "Avoided Frequency" overlap.
11
11-10 | CFW100
0.0 to 300.0 Hz
0.0 to 300.0 Hz
0.0 to 25.0 Hz
Output
frequency
P304
P303
Figure 11.9: Actuation of the avoided frequency
Figure 11.9 on page 11-10
2 x P306
2 x P306
Reference
Return
Advance
Factory
0.0 Hz
Setting:
Factory
0.0 Hz
Setting:
Factory
0.0 Hz
Setting:
below.