WEG CFW100 Programming Manual page 32

V2.4x
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

Programming Basic Instructions
P208 – Reference Scale Factor
Adjustable
Range:
Properties:
Description:
This parameter allows adjusting the scale of the parameter speed reference P001 and output (motor) speed
P002 so as to convert the indication of frequency values applied to the motor (Hz) into angular speed in "rpm"
or a proportional value in "%", for instance.
Together with the unit in P209 and the decimal places in P210, the rated reference (P208) defines the speed
indication on the inverter HMI. According to the factory default of those parameters, the preset scale on the
inverter is in "Hz" and with a decimal place (60.0 Hz or 50.0 Hz). On the other hand, by setting P208 = 1800
or 1500, P209 = 3 and P210 = 0, a scale in "rpm" with no decimal places is defined (1800 rpm or 1500 rpm).
5
P209 – Reference Engineering Unit
Adjustable
Range:
Properties:
Description:
This parameter selects the engineering unit that will be presented on parameters P001 and P002.
P210 – Reference Indication Form
Adjustable
Range:
Properties:
Description:
This parameter allows setting the form of indication of parameters P001 and P002.
P213 – Bar Graph Scale Factor
Adjustable
Range:
Properties:
Description:
This parameter configures the full scale (100 %) of the bar graph to indicate the parameter selected by P207.
5-2 | CFW100
1 to 9999
0 = Without Unit
1 = Without Unit
2 = Volts (V)
3 = Hertz (Hz)
4 = Without Unit
5 = Percent (%)
6 = Without Unit
7 = Rotation/min. (rpm)
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
1 to 9999
Return
Advance
Factory
P208 = 600
Setting:
(500)
Factory
3
Setting:
Factory
1
Setting:
Factory
52
Setting:

Hide quick links: