WEG CFW100 Programming Manual page 45

V2.4x
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

Multispeed: refer to
section 12.5 DIGITAL INPUT on page 12-8.
AI1 > 0: the negative values of the AI1 reference are zeroed.
CO / DN: interface CANopen or DeviceNet.
P223 – FORWARD/REVERSE Selection - LOCAL Situation
P226 – FORWARD/REVERSE Selection – REMOTE Situation
Adjustable
0 = Always FORWARD
1 = Always REVERSE
Range:
2 = Not Used
3 = Not Used
4 = DIx
5 = Serial/USB (FWD)
6 = Serial/USB (REV)
7 to 8 = Not Used
9 = CO/DN (FWD)
10 = CO/DN (REV)
11 = Not Used
12 = SoftPLC
Properties:
cfg
Description:
They define the origin source for the "Direction of Rotation" command in the Local and Remote situation, where:
H: Means Forward.
AH: Means Reverse.
DIx: refer to
section 12.5 DIGITAL INPUT on page
CO / DN: interface CANopen or DeviceNet.
P224 – Run / Stop Selection – LOCAL Situation
P227 – Run / Stop Selection – REMOTE Situation
Adjustable
0 = HMI Keys
1 = DIx
Range:
2 = Serial/USB
3 = Not Used
4 = CO/DN
5 = SoftPLC
Properties:
cfg
Description:
These parameters define the origin source for the "Run/Stop" command in the Local and Remote situation.
This command corresponds to the functions implemented in any of the command sources able to enable the
motor movement, that is, genera enable, ramp enable, forward run, reverse run, start, etc.
Logical Command and Speed Reference
12-8.
Return
Advance
Factory
P223 = 0
Setting:
P226 = 2
Factory
P224 = 0
Setting:
P227 = 3
CFW100 | 7-5
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents