Faults and Alarms

13.12 EXTERNAL ALARM (A090)

It is necessary to set the digital input Dix for "without external alarm". If DIx is inactive, the inverter will activate the
external alarm A090. When DIx is activated, the alarm message will automatically disappear from the HMI display.
The motor keeps running normally, regardless the state of this input.

13.13 EXTERNAL FAULT (F091)

It is necessary to set the digital input Dix for "without external fault". If DIx is inactive, the inverter will activate the
external fault F091. In this case, the PWM pulses are immediately disabled.

13.14 FAULT HISTORY

The inverter is able to store a set of data on the last three faults occurred, such as: fault number, current (P003),
DC link voltage (P004), output frequency (P005), power module temperature (P030).
P048 – Present Alarm
P049 – Present Fault
Adjustable
Range:
Properties:
Description:
They indicate the alarm number (P048) or the fault (P049) that may be present in the inverter.
P050 – Last Fault
P060 – Second Fault
P070 – Third Fault
Adjustable
Range:
Properties:
Description:
They indicate the number of the occurred fault.
P051 – Output Current Last Fault
Adjustable
13
Range:
Properties:
Description:
They indicate the output current at the moment of the occurred fault.
P052 – Last Fault DC Link
Adjustable
Range:
Properties:
13-4 | CFW100
0 to 999
ro
0 to 999
ro
0.0 to 10.0 A
ro
0 to 524 V
ro
Return
Advance
Factory
Setting:
Factory
Setting:
Factory
Setting:
Factory
Setting: