WEG CFW100 Programming Manual

WEG CFW100 Programming Manual

Micro mini drives
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
Micro Mini Drives
Programming Manual

Advertisement

Table of Contents
loading

Summary of Contents for WEG CFW100

  • Page 1 Motors | Automation | Energy | Transmission & Distribution | Coatings Frequency Inverter Micro Mini Drives Programming Manual...
  • Page 3 Programming Manual Language: English Document: 123456789AB / 00 Build 1414 Publication Date: 12/2018...
  • Page 4 SUMMARY OF REVISIONS The information below describes the reviews made in this manual. Revision Description First Edition Applied to CFW100 frequency inverters version V3.00 or newer Applied to CFW300 frequency inverters version V2.00 or newer...
  • Page 5: Table Of Contents

    CONTENTS QUICK REFERENCE OF ALARMS AND FAULTS ......2 SAFETY NOTICES ..............2.1 SAFETY NOTICES IN THIS MANUAL .
  • Page 6 CONTENTS 9.3 SIGNAL POTENTIOMETER INPUT ..............9-5 9.4 ANALOG OUTPUTS .
  • Page 7 QUICK REFERENCE OF PARAMETERS QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P000 Access to Parameters 0 to 9999 P001 Speed Reference 0 to 9999 11-1 P002 Output Speed (Motor) 0 to 9999 11-1 P003 Motor Current 0.0 to 40.0 A 11-1 P004 DC Link Voltage...
  • Page 8 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P037 Motor Overload Ixt 0.0 to 100.0 % 10-4 P038 Encoder Speed -9999 to 9999 rpm 11-4 P039 Encoder Pulses Count 0 to 9999 11-4 P045 Fan Enabled Time 0 to FFFF (hexa) 11-5 P047 CONF Status...
  • Page 9 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P150 DC/LC Regul. Type 0 = hold_Ud and decel_LC cfg, V/f, VVW 1 = accel_Ud and decel_LC 2 = hold_Ud and hold_LC 3 = accel_Ud and hold_LC P151 DC Link Regul. Level 325 to 810 V V/f, VVW P153...
  • Page 10 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P223 LOC FWD/REV Selection 0 = Foward 1 = Reverse 2 to 3 = Not Used 4 = DIx 5 = Serial/USB (FWD) 6 = Serial/USB (REV) 7 to 8 = Not Used 9 = CO/DN/DP/ETH (FWD) 10 = CO/DN/DP/ETH (REV) 11 = Not Used...
  • Page 11 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P245 Potentiometer and FI1 Filter 0.00 to 16.00 s P246 FI1 Input Function 0 = Inactive 9-11 1 = Active in DI1 2 = Active in DI2 3 = Active in DI3 4 = Active in DI4 P247 FI1 Input Gain...
  • Page 12 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P263 DI1 Input Function 0 = Not Used 9-12 1 = Run/Stop 2 = General Enable 3 = Quick Stop 4 = Foward Run 5 = Reverse Run 6 = Start 7 = Stop 8 = Direction of Rotation 9 = LOC/REM...
  • Page 13 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P264 DI2 Input Function 0 = Not Used 9-12 1 = Run/Stop 2 = General Enable 3 = Quick Stop 4 = Foward Run 5 = Reverse Run 6 = Start 7 = Stop 8 = Direction of Rotation 9 = LOC/REM...
  • Page 14 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P265 DI3 Input Function 0 = Not Used 9-12 1 = Run/Stop 2 = General Enable 3 = Quick Stop 4 = Foward Run 5 = Reverse Run 6 = Start 7 = Stop 8 = Direction of Rotation 9 = LOC/REM...
  • Page 15 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P266 DI4 Input Function 0 = Not Used 9-12 1 = Run/Stop 2 = General Enable 3 = Quick Stop 4 = Foward Run 5 = Reverse Run 6 = Start 7 = Stop 8 = Direction of Rotation 9 = LOC/REM...
  • Page 16 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P275 DO1 Function 0 = Not Used 9-21 1 = F* ≥ Fx 2 = F ≥ Fx 3 = F ≤ Fx 4 = F = F* 5 = Not Used 6 = Is >...
  • Page 17 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P311 Serial Bytes Config. 0 = 8 bits, no, 1 12-2 1 = 8 bits, even,1 2 = 8 bits, odd, 1 3 = 8 bits, no, 2 4 = 8 bits, even,2 5 = 8 bits, odd, 2 P312 Serial Protocol...
  • Page 18 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P580 Fire Mode Configuration 0 = Inactive 8-16 1 = Active 2 = Active / P134 3 = Reserved 4 = Active / General Disable P582 Fire Mode Auto-reset Adjustable 0 = Limited 8-16 1 = Unlimited...
  • Page 19 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P702 CAN Baud Rate 0 = 1 Mbps/Auto 12-4 1 = Reserved/Auto 2 = 500 Kbps 3 = 250 Kbps 4 = 125 Kbps 5 = 100 Kbps/Auto 6 = 50 Kbps/Auto 7 = 20 Kbps/Auto 8 = 10 Kbps/Auto P703...
  • Page 20 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P749 Profibus Write Word#6 0 to 1199 12-7 P750 Profibus Address 1 to 126 12-7 P751 Profibus Teleg. Sel. 1 = Std. Teleg. 1 12-7 2 = Telegram 100 3 = Telegram 101 4 = Telegram 102 5 = Telegram 103 P754...
  • Page 21 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P881 Write Word #4 Ethernet 0 to 9999 12-10 P882 Write Word #5 Ethernet 0 to 9999 12-10 P883 Write Word #6 Ethernet 0 to 9999 12-10 P884 Write Word #7 Ethernet 0 to 9999 12-10 P885...
  • Page 22 QUICK REFERENCE OF PARAMETERS Param. Description Adjustable Range Prop. Page P947 SoftPLC Parameter 38 -9999 to 9999 13-4 P948 SoftPLC Parameter 39 -9999 to 9999 13-4 P949 SoftPLC Parameter 40 -9999 to 9999 13-4 P950 SoftPLC Parameter 41 -9999 to 9999 13-4 P951 SoftPLC Parameter 42...
  • Page 23: Quick Reference Of Alarms And Faults

    High ambient temperature around the inverter and high output current. For further information, refer to of the user’s manual available for download on the website: www.weg.net. Blocked or defective fan. Heatsink is too dirty, preventing the air flow. F051 Overtemperature fault measured on High temperature at IGBTs.
  • Page 24 QUICK REFERENCE OF ALARMS AND FAULTS Fault / Alarm Description Possible Causes F081 Fault of end of memory to save user’s Attempt to save (P204 = 9) more than 32 parameters End of User’s Memory parameter table. (with values different from the factory default) on the User parameter table.
  • Page 25 QUICK REFERENCE OF ALARMS AND FAULTS Fault / Alarm Description Possible Causes A147 It indicates interruption in the cyclic Check the status of the network master. EtherNet/IP Communication communication with EtherNet/IP Check the network installation, broken cable or failed/bad Offline master.
  • Page 26 QUICK REFERENCE OF ALARMS AND FAULTS Fault / Alarm Description Possible Causes F239 It indicates an interruption in the Check if the network master is correctly configured and Offline Profibus DP Interface communication between the Profibus operating properly. DP network master and the inverter. Check short-circuit poor...
  • Page 27 QUICK REFERENCE OF ALARMS AND FAULTS Faults and Alarms for PID Controller Application (P903 = 1) Fault / Alarm Description Possible Causes A750 It indicates that the PID Controller is in The motor speed remained below the value programmed in Sleep Mode Active the sleep mode.
  • Page 28: Safety Notices

    SAFETY NOTICES 2 SAFETY NOTICES This manual contains the information necessary for the correct frequency inverter programming. It was developed to be used by people with proper technical training or qualification to operate this kind of equipment. These people must follow the safety instructions defined by local standards. The noncompliance with the safety instructions may result in death risk and/or equipment damage.
  • Page 29: Preliminary Recommendations

    SAFETY NOTICES 2.3 PRELIMINARY RECOMMENDATIONS DANGER! Only qualified personnel familiar with the frequency inverter and associated equipment should plan or implement the installation, start-up and subsequent maintenance of this equipment. These personnel must follow all the safety instructions included in this manual and/or defined by local regulations.
  • Page 30: General Information

    GENERAL INFORMATION 3 GENERAL INFORMATION This manual presents information necessary for the configuration of all the functions and parameters of the frequency inverter. This manual must be used together with the user’s manual. The text provides additional information so as simplify the use and programming of the frequency inverter in certain applications.
  • Page 31: Numerical Representation

    V: volts; electric voltage unit. WPS: Programming Software “WEG Programming Suite”. Ω: ohms; electric resistance unit. 3.1.2 Numerical Representation The decimal numbers are represented by means of digits without suffix. Parameters P012, P013, P045, P397 P680, P682, P684, P685, P690, P695, P697, P757, P758 and P840 are represented in hexadecimal numbers.
  • Page 32: About The Hmi

    ABOUT THE HMI 4 ABOUT THE HMI 4.1 USE OF THE HMI TO OPERATE THE INVERTER Using the HMI, it is possible to command the inverter, view and adjust all of its parameters. The HMI presents the following functions: Enables/Disables the inverter via Selects (switches) between the acceleration/deceleration ramp parameter number and its value...
  • Page 33 ABOUT THE HMI Table 4.1: HMI operating modes Start-up Mode It is the initial status of the HMI after the successful power-up (without fault, alarms or undervoltages) Monitoring Press the key to go to level 1 of the setting mode - parameter selection. Pressing any other key will also change to the setting mode Setting Mode Level 1:...
  • Page 34: Hmi

    5 HMI ✓ NOTE! The inverter comes from the factory with the frequency (V/f 50/60 Hz mode) and voltage adjusted according to the market. The reset to factory default may change the content of the parameters related to frequency. 5.1 ACCESS Whenever the inverter is powered up, the HMI display goes to the start-up mode if no faults, alarms or undervoltages are present.
  • Page 35 Not Used: no action Load WEG 60 Hz: it loads the default parameters on the inverter with the factory default for 60 Hz Load WEG 50 Hz: it loads the default parameters on the inverter with the factory default for 50 Hz...
  • Page 36: Indications

    ✓ NOTE! In order to upload the user parameters (P204 = 7), the factory default must be uploaded first (P204 = 5 or 6). 5.2 INDICATIONS P205 - Main Display Parameter Range: 0 to 999 Description: This parameter defines which parameter will be viewed on the HMI when the motor is enabled after initialization. P207 - Bar Graph Parameter Range: 0 to 999...
  • Page 37 P210 - Ref. Decimal Point P511 - SoftPLC Indication Form Range: 0 = wxyz 1 = wxy.z 2 = wx.yz 3 = w.xyz Description: This parameter allows setting the position of the decimal point displayed on the HMI. P210 is linked to the indication of parameters P001 and P002.
  • Page 38: Frequency Inverter Identification

    FREQUENCY INVERTER IDENTIFICATION 6 FREQUENCY INVERTER IDENTIFICATION In order to check the inverter model, see the code on the product nameplate on the side of the inverter. Once verified the identification code of the model of the inverter, refer to Chapter 2 General Information of the user’s manual of the frequency inverter.
  • Page 39 For these models, P296 must be adjusted in accordance with the mains voltage used, and the parameter P295 will be changed automatically by the inverter. For more information, refer to the user manual, available for download on www.weg.net. P295 - Inverter Rated Current Range: 1.1 to 15.2 A...
  • Page 40: Accessories

    ✓ NOTE! 200 V Line: P296 is read-only parameter (ro). 400 V Line: P296 is configuration parameter (cfg). For further information, refer to the user’s manual, available for download on: www.weg.net. P613 - Main SW Revision Range: -9999 to 9999...
  • Page 41: Reference Source Selection

    COMMAND AND REFERENCES 7 COMMAND AND REFERENCES The drive of the electric motor connected to the inverter depends on the logical command and on the reference defined by one of the several possible sources, such as: HMI keys, digital inputs (DIx), analog inputs (AIx), Serial/ USB interface, CANopen/DeviceNet interface, SoftPLC, etc.
  • Page 42 COMMAND AND REFERENCES Direction of rotation Run/ Stop Control word Control word Direction of rotation Control word Run/ Stop All the command and reference sources of the Inverter LOC/REM 2nd Ramp Reference Frequency Reference frequency Reference Frequency Figure 7.1: Block diagram for commands and references 7-2 | Micro Mini Drives...
  • Page 43 COMMAND AND REFERENCES Command selection frequency P221 or P222 Reference HMIR key (P121) 0 - HMI CRS485 Accessory 7 - EP DI1 to DI4 P247 P249 Accel. Decel. 4 - FI 17 - FI > 0 Electronic Potentiometer Frequency reference of P124 to P131 the inverter 8 - Multispeed...
  • Page 44 COMMAND AND REFERENCES P220 - LOC/REM Selection Source Range: 0 = Always Local 1 = Always Remote 2 to 3 = Not Used 4 = DIx 5 = Serial/USB (LOC) 6 = Serial/USB (REM) 7 to 8 = Not Used 9 = CO/DN/DP/ETH (LOC) 10 = CO/DN/DP/ETH (REM) 11 = SoftPLC...
  • Page 45 COMMAND AND REFERENCES HMI: the reference value set by the keys and are contained in parameter P121. E.P.: electronic potentiometer, refer to Section 9.6 DIGITAL INPUTS on page 9-11. Multispeed: refer to Section 9.6 DIGITAL INPUTS on page 9-11. AIx > 0: the negative values of the AIx reference are zeroed. CO / DN / DP / ETH: interface CANopen, DeviceNet, Profibus DP or Ethernet.
  • Page 46: Speed Reference

    COMMAND AND REFERENCES P225 - LOC JOG Selection P228 - REM JOG Selection Range: 0 = Disabled 1 = Not Used 2 = DIx 3 = Serial/USB 4 = Not Used 5 = CO/DN/DP/ETH 6 = SoftPLC Properties: Description: They define the origin source for the JOG function in the Local and Remote situation. The JOG function means a Run/Stop command added to the reference defined by P122.
  • Page 47 COMMAND AND REFERENCES In general, the digital references defined by parameters such as: HMI keys (P121), Multispeed (P124 to P131) and E.P. have a scale from 0.0 to 400.0 Hz with resolution of 0.1 Hz. In digital inputs (DIx), on the other hand, the reference is defined according to the function predefined for P263 to P266.
  • Page 48 COMMAND AND REFERENCES Besides, the P121 is used as input for the reference backup function. ✓ NOTE! The minimum and maximum values of parameter setting are limited by P134 and P133, respectively. P122 - JOG Reference Range: -400.0 to 400.0 Hz Description: During the JOG command, the motor accelerates up to the value defined in P122, following the acceleration ramp set according to P105.
  • Page 49 COMMAND AND REFERENCES Table 7.4: Multispeed frequency reference 8 Referency 4 Referency 2 Referency DI1 or DI2 or DI5 or DI6 DI3 or DI7 DI4 or DI8 Frequency Reference Inactive Inactive Inactive P124 Inactive Inactive Active P125 Inactive Active Inactive P126 Inactive Active...
  • Page 50: Motor Control

    MOTOR CONTROL 8 MOTOR CONTROL The inverter feeds the motor with variable voltage, current and frequency, providing control of the motor speed. The values applied to the motor follow a control strategy, which depends on the selected type of motor control and on the inverter parameter settings.
  • Page 51 MOTOR CONTROL ✓ NOTE! The setting with too short ramp time may cause overcurrent in the output (F070), undervoltage (F021) or overvoltage (F022) of the DC link. P100 - Acceleration Time P101 - Deceleration Time P102 - Acceleration Time 2nd Ramp P103 - Deceleration Time 2nd Ramp P106 - Emer.
  • Page 52: Regulation

    MOTOR CONTROL P105 - 1st / 2nd Ramp Selection Range: 0 = 1st Ramp 1 = 2nd Ramp 2 = DIx 3 = Serial/USB 4 = Reserved 5 = CO/DN/DP/ETH 6 = SoftPLC Description: It defines the origin source of the command to select between the first and second Ramp. Note: Parameter P680 (Logical Status) indicates if the 2 Ramp is active or not.
  • Page 53: Dc Link Voltage Limitation By "Accelerate Ramp" (P150 = 1 Or 3)

    MOTOR CONTROL Actuation: when the DC link voltage reaches the level set in P151, a command is sent to the ”ramp” block, which inhibits the motor frequency variation according to Figure 8.12 on page 8-19 Figure 8.20 on page 8-27. Use recommended in the drive of loads with high moment of inertia referred to the motor shaft or loads that require short deceleration ramps.
  • Page 54 MOTOR CONTROL Another condition that prevents the output voltage from reaching its maximum value is internal losses of the inverter. Such losses are associated to the dead time of the switching and losses in the components, being aggravated by the increase of the switching frequency. Such conditions, variations in the DC Link voltage and internal losses can be compensated with variations in the modulation index;...
  • Page 55 MOTOR CONTROL Figure 8.3 on page 8-6 shows the block diagram of the actuation of the limitation. Figure 8.4 on page 8-6 Figure 8.5 on page 8-7 show the example chart. Ramp P100-P104 Reference Output frequency P101 P002 Hold ≥ 0 P004 P151 Figure 8.3: Block diagram DC Link voltage limitation...
  • Page 56: Output Current

    MOTOR CONTROL DC Link voltage (P004) F022 - overvoltage P151 DC Link regulation rated Time Output frequency Time Figure 8.5: Example graph of the DC Link voltage limitation - Accelerate Ramp (P150 = 0 or 1) 8.1.2.2 Output Current Like in the DC Link voltage regulation, the output current regulation also has two operating modes: ”Ramp Holding” (P150 = 2 or 3) and ”Decelerate Ramp”...
  • Page 57: Switching Frequency

    MOTOR CONTROL Current level to activate the current limitation for the Ramp Hold and Decelerate Ramp modes, as per Figure 8.6 on page 8-8 (a) and (b), respectively. In order to disable the current limitation, you must set parameter P135 > 1.9 Motor current Motor current P135...
  • Page 58: Flying Start / Ride-Through

    MOTOR CONTROL Description: It defines the point at which automatic gradual reduction of the switching frequency occurs. That significantly improves the measurement of the output current at low frequencies and consequently the performance of the inverter. ✓ NOTE! Both the function related to P219 and the function controlled by P397 (bit 3) act by reducing the switching frequency.
  • Page 59: Dc Braking

    MOTOR CONTROL application. Ride-Through Function (RT): The Ride-Through function will disable the inverter output pulses (IGBT) as soon as the supply voltage reaches a value below the undervoltage value. A fault due to undervoltage (F021) does not occur and the DC link voltage will slowly drop until the supply voltage returns. In case it takes the supply voltage too long to return (over 2 seconds), the inverter may indicate F021 (undervoltage on the DC link).
  • Page 60 MOTOR CONTROL P299 - DC Braking Start Time Range: 0.0 to 15.0 s Properties: V/f, VVW Description: DC braking duration at the start. Output frequency Time Direct current injection at start P299 P302 DC braking Time Stop Figure 8.8: DC Braking actuation at start P300 - DC Braking Stop Time Range: 0.0 to 15.0 s...
  • Page 61: Dynamic Braking

    MOTOR CONTROL WARNING! The DC Braking can continue acting even if the motor has already stopped. Be careful with the thermal dimensioning of the motor for short-period cyclic braking. P301 - DC Braking Frequency Range: 0.0 to 15.0 Hz Properties: V/f, VVW Description: This parameter establishes the initial point to apply the DC Braking at the stop when the inverter is disabled by...
  • Page 62: Skip Frequency

    MOTOR CONTROL The parameter P153 defines the voltage level for the braking IGBT actuation, and it must be compatible with the power supply voltage. If P153 is set at a level too close to the overvoltage actuation level (F022), it may occur before the braking resistor can dissipate the motor regenerated energy.
  • Page 63: Fire Mode

    MOTOR CONTROL P304 - Skip Frequency 2 Range: 0.0 to 400.0 Hz Properties: V/f, VVW Description: These parameters represent the center of the frequency range avoided, according to Figure 8.11 on page 8-14. P306 - Skip Band Range: 0.0 to 25.0 Hz Properties: V/f, VVW Description:...
  • Page 64 It is essential to follow the aforementioned instructions before using the frequency inverter in the ”Fire Mode” function. Under no circumstance shall WEG take any liability for deaths, damages, compensations and/or losses occurred due to the improper programming or operation of the frequency inverter in the ”Fire Mode”...
  • Page 65: Control Configuration

    MOTOR CONTROL P580 - Fire Mode Configuration Range: 0 = Inactive 1 = Active 2 = Active / P134 3 = Reserved 4 = Active / General Disable Properties: Description: This parameter defines how the Fire Mode functionality will work in the frequency inverter. Table 8.3: Options for the parameter P580 Option Description...
  • Page 66 WARNING! The default setting of P397 meets most application needs of the inverter. Therefore, avoid modifying its content without knowing the related consequences. If you are not sure, contact WEG Technical Assistance before changing P397. Table 8.5: Options available to configure the control (P397)
  • Page 67: V/F

    MOTOR CONTROL 8.2 V/F This is the classical control method for three-phase induction motors, based on a curve that relates output frequency and voltage. The inverter works as a variable frequency and voltage source, generating a combination of voltage and frequency according to the configured curve. It is possible to adjust this curve for standard 50 Hz, 60 Hz or special motors.
  • Page 68 MOTOR CONTROL Figure 8.12: Block diagram of V/f scale control Micro Mini Drives | 8-19...
  • Page 69 MOTOR CONTROL The V/f curve is completely adjustable in four different points as according to Figure 8.13 on page 8-20, although the factory default set a curve pre-adjusted for motors 50 Hz or 60 Hz, as options for P204. This format, point P defines the amplitude applied at 0 Hz, while P defines the rated amplitude and frequency and beginning of field weakening.
  • Page 70 MOTOR CONTROL Sequence for installation, verification, power up and start-up: 1. Install the inverter: according to chapter 3 Installation and Connection of the user’s manual, making all the power and control connections. 2. Prepare and power up the inverter according to Section 3.2 Electrical Installation of the user’s manual of the frequency inverter.
  • Page 71 MOTOR CONTROL Output voltage (%) P142 P136 P145 P134 Output frequency (Hz) Figure 8.16: Torque boost region for quadratic V/f control mode P137 - Automatic Torque Boost Range: 0.0 to 30.0 % Properties: Description: The automatic torque boost compensates the voltage drop in the stator resistance because of active current. Look at Figure 8.12 on page 8-19, where variable IxR corresponds to the automatic torque boost action on the...
  • Page 72 MOTOR CONTROL compensates the speed drop due to the application of load on the shaft and, consequently, the slip. Thus, it increments the output frequency (Δf) considering the increase of the motor active current, as shown in Figure 8.18 on page 8-23.
  • Page 73: Energy Saver (Eoc)

    MOTOR CONTROL 8.2.1 Energy Saver (EOC) The efficiency of a machine is defined as being the ratio between the output mechanical power and the input electrical power. Remember that the mechanical power is the product between torque and rotor speed, and that the input electric power is the sum of the output mechanical power and the motor losses.
  • Page 74: Vvw

    8.3 VVW The VVW vector control mode (Voltage Vector WEG) uses a control method with a much higher performance than the V/f control because of the load torque estimation and of the control of the magnetic flux in the air gap, as per...
  • Page 75 MOTOR CONTROL scheme of Figure 8.20 on page 8-27. In this control strategy, losses, efficiency, rated slip and power factor of the motor are considered in order to improve the control performance. The main advantage compared to the V/f control is the best frequency regulation with greater torque capacity at low speeds (frequencies below 5 Hz), allowing a relevant improvement in the drive performance in permanent duty.
  • Page 76 MOTOR CONTROL Figure 8.20: VVW control flow Micro Mini Drives | 8-27...
  • Page 77 Below are described the parameters to configure the VVW vector control setting. This data is easily obtained on WEG standard motor nameplates, however in older motors or motors made by other manufacturers, the data may not be readily available.
  • Page 78 MOTOR CONTROL Table 8.6: Characteristics of IV pole WEG standard motors (indicative values) Power Voltage Current Frequency Speed Efficiency Stator Frame Power [P400] [P401] [P403] [P402] [P399] Resistance [P409] (HP) (kW) Size Factor (Hz) (rpm) (Ω) 0.16 0.12 0.85 1720 56.0...
  • Page 79 5. Also set the value of P409. If any of these data is not available, enter the approximate value by calculations or by similarity to the WEG standard motor, see the Self-Tuning of the VVW control: the self-tuning is activated by setting P408 = 1.
  • Page 80 MOTOR CONTROL Indication on the Display / Action Indication on the Display / Action Initialization mode Press the keys until selecting parameter P296 Press this key to enter the first level of the setting mode If necessary, change the content of “P296 - Line Rated Press the key to change the content of “P202 - Voltage”...
  • Page 81 MOTOR CONTROL P178 - Rated Flux Range: 50.0 to 150.0 % Properties: Description: It defines the desired flux in the motor air gap in percentage (%) of the rated flux. In general, it is not necessary to modify the value of P178 of the standard value of 100,0 %. However, some specific situations may use values slightly above to increase the torque, or below to reduce the energy consumption.
  • Page 82 MOTOR CONTROL ✓ NOTE! It is not recommended setting the motor rated current greater than inverter rated current (P295). P402 - Motor Rated Speed Range: 0 to 24000 rpm Properties: cfg, VVW Description: It defines the rated motor speed. Parameter P402 must be set according to the information on the motor nameplate. The setting of parameter P402 via HMI for values above 9999 rpm is performed from 10.00 to 30.00 rpm (x 1000).
  • Page 83 MOTOR CONTROL It sets the number of pulses per revolution (ppr) of the incremental encoder. This parameter influences the indication of the speed parameters (P038) and pulse counter (P039) of the encoder. ✓ NOTE! Parameter P405 is only visible on the HMI if the IOAENC expansion module is connected to the inverter.
  • Page 84: Analog Inputs

    9 I/O This chapter contains the parameters for setting the inverter inputs and outputs. This setting depends on the accessory connected to the product. ✓ NOTE! The inverter HMI only displays the parameters related to the resources available in the accessory connected to the product.
  • Page 85 reference from the minimum point (0 V / 0 mA / 4 mA or 10 V / 20 mA), and it will be directly related to the minimum frequency set in P133. Check Figure 9.2 on page 9-2. If the parameter is set as Active (P230 = 1), the signal in the analog inputs will have a dead zone, where the frequency reference remains at the Minimum frequency value (P133), even with the variation of the input signal.
  • Page 86 the description of those parameters in Chapter 7 COMMAND AND REFERENCES on page 7-1. Option 4 (PTC) configures the input to monitor the motor temperature. For further details on this function, refer to Section 10.3 PROTECTIONS on page 10-3. Option 7 (PLC Use), as well as options 8 to 15, configures the input to be used by the programming done in the memory area reserved for the SoftPLC function.
  • Page 87 Table 9.1: Alx configuration and equation Signal P233 or P238 Equation AIx(%) AIx(V) 0 to 10 V AIx(%) = x (100,0 %) + offset x gain 10 V AIx(mA) 0 to 20 mA AIx(%) = x (100,0 %) + offset x gain 20 mA AIx(mA) - 4 mA...
  • Page 88: Ntc Sensor Input

    P240 - AI2 Input Filter Range: 0.00 to 16.00 s Description: These parameters define the times of the analog input filters. 9.2 NTC SENSOR INPUT Depending on the inverter (see the user’s manual), there is an expansion module that has an exclusive analog input to connect an NTC sensor.
  • Page 89: Analog Outputs

    The indicated values are obtained after the offset action and the multiplication by the gain. P241 - Potentiometer Signal Function Range: 0 = Speed Ref. 1 to 6 = Not Used 7 = SoftPLC 8 = Application Function 1 9 = Application Function 2 10 = Application Function 3 11 = Application Function 4 12 = Application Function 5...
  • Page 90 AO1 - P014 AO2 - P015 Signal Function Gain AO1 - P253 AO1 - P251 AO1 - P252 AO2 - P256 AO2 - P254 AO2 - P255 Value (*) Control terminals available on the accessory. Figure 9.4: Block diagram of the analog output (AOx) P014 - AO1 Value P015 - AO2 Value Range:...
  • Page 91 P254 - AO2 Output Function Range: 0 = Speed Ref. 1 = Not Used 2 = Real Speed 3 to 4 = Not Used 5 = Output Current 6 = Not Used 7 = Active Current 8 to 10 = Not Used 11 = Motor Torque 12 = SoftPLC 13 to 15 = Not Used...
  • Page 92 Description: It determines the analog outputs gain according to the equations of Table 9.3 on page 9-9. P253 - AO1 Output Signal P256 - AO2 Output Signal Range: 0 = 0 to 10 V 1 = 0 to 20 mA 2 = 4 to 20 mA 3 = 10 V to 0 4 = 20 mA to 0...
  • Page 93: Frequency Input

    9.5 FREQUENCY INPUT A frequency input consists of a fast digital input able to convert the frequency of the pulses in the input into a proportional signal with 15-bit resolution. After the conversion, this signal is used as an analog signal for frequency reference, process variable, for example.
  • Page 94: Digital Inputs

    ✓ NOTE! The operation of parameters P022 as well as of the frequency input, depends on the configuration of the parameter P246. P246 - FI1 Input Function Range: 0 = Inactive 1 = Active in DI1 2 = Active in DI2 3 = Active in DI3 4 = Active in DI4 Properties:...
  • Page 95 P012 - DI8 to DI1 Status Range: 0 to FF (hexa) Bit 0 = DI1 Bit 1 = DI2 Bit 2 = DI3 Bit 3 = DI4 Bit 4 = DI5 Bit 5 = DI6 Bit 6 = DI7 Bit 7 = DI8 Properties: Description: Using this parameter, it is possible to view the status of the digital inputs, according to the IO’s expansion accessory...
  • Page 96 P270 - DI8 Input Function Range: 0 = Not Used 1 = Run/Stop 2 = General Enable 3 = Quick Stop 4 = Foward Run 5 = Reverse Run 6 = Start 7 = Stop 8 = Direction of Rotation 9 = LOC/REM 10 = JOG 11 = Accelerate E.P.
  • Page 97 Table 9.5: Digital Input Functions Value Description Dependence Figure (Page) Not used Run/Stop command P224 = 1 or P227 = 1 9.6 (9-15) General Enable command 9.7 (9-15) Fast Stop P224 = 1 or P227 = 1 9.8 (9-15) (P224 = 1 and P223 = 4) or Forward run command 9.9 (9-16) (P227 = 1 and P226 = 4)
  • Page 98 P271 - DIs Function Range: 0 = (DI1..DI8) NPN 1 = (DI1..DI4) PNP 2 = (DI5..DI8) PNP 3 = (DI1..DI8) PNP Properties: Description: It configures the default for the digital input signal, that is, NPN and the digital input is activated with 0 V, PNP and the digital input is activated with +24 V.
  • Page 99 d) FORWARD/REVERSE COMMAND This function is the combination of two DIS: one programmed for forward run and the other for reverse run (Figure 9.9 on page 9-16). Active DIx - Forward Active Time Active DIx - Reverse Active Time Output Forward frequency Time...
  • Page 100 Forward Output frequency Time Reverse Active Inactive Time Figure 9.11: Example of the Direction of Rotation function g) LOCAL / REMOTE If DIx is inactive, the Local command is selected, reverse the Remote command is selected. h) JOG The JOG command is the combination of the Run/Stop command with a speed reference via parameter P122 (Figure 9.12 on page 9-17).
  • Page 101 DIx - Accelerate RAMP Reference DIx - Decelerate Reset Speed & Enabling (RUN) P133 Output frequency Time Active DIx - Accelerate Inactive Reset Time Active DIx - Decelerate Inactive Time Active DIx - Run/Stop Inactive Time Figure 9.13: Example of the Electronic Potentiometer (E.P.) function j) MULTISPEED The Multispeed reference, as described in Section 7.2 SPEED REFERENCE on page...
  • Page 102 n) FAULT RESET Once the inverter is with the fault state active, and the fault origin condition is no longer active. The reset of the fault state will occur when the DIx set for this function is active. o) DISABLE FLYING START It allows the DIx, when active, to disable the action of the Flying Start function preset in parameter P320 = 1 or 2.
  • Page 103: Input For Infrared Receiver

    Deceleration Output ramp frequency Time Active DIx - Safety switch Inactive Time Figure 9.17: Example of the Emergency function 9.7 INPUT FOR INFRARED RECEIVER The IOADR accessory uses an infrared remote control to control the inverter. The RC-5 protocol (Philips) was used for the communication of the control with the accessory.
  • Page 104 The P013 value is indicated in hexadecimal, where each bit of the number indicates the status of a digital output, that is, if Bit0 is ”0”, DO1 is inactive; if Bit0 is ”1”, DO1 is active, and so on, up to DO4. ✓...
  • Page 105 P278 - DO4 Function Range: 0 = Not Used 1 = F* ≥ Fx 2 = F ≥ Fx 3 = F ≤ Fx 4 = F = F* 5 = Not Used 6 = Is > Ix 7 = Is < Ix 8 = Torque >...
  • Page 106 Table 9.6: Digital Output Functions Value Function Description Not Used It deactivates the digital output F* ≥ Fx Active when the frequency reference F* (P001) is greater or iqual the Fx (P281) F ≥ Fx Active when the Output Frequency F (P002) is greater or iqual the Fx (P281) F ≤...
  • Page 107 Properties: Description: Parameters used for monitoring and controlling the inverter by using the communication interfaces. For a detailed description, refer to the user manual of the communication network, available for download on the website: www.weg.net. 9-24 | Micro Mini Drives...
  • Page 108: Faults And Alarms

    FAULTS AND ALARMS 10 FAULTS AND ALARMS The problem detection structure in the inverter is based on the fault and alarm indication. In case of fault, the locking the IGBTs and motor stop by inertia will occur. The alarm works as a warning for the user of critical operating conditions and that may cause a fault if the situation is not corrected.
  • Page 109: Fault Control

    FAULTS AND ALARMS It indicates the DC link voltage at the moment of the last occurred fault. P053 - Frequency At Last Fault Range: 0.0 to 400.0 Hz Properties: Description: If indicates the output frequency at the moment of the last occurred fault. P054 - Temperature Last Fault Range: 0.0 to 200.0 ºC...
  • Page 110: Protections

    FAULTS AND ALARMS P358 - Encoder Fault Config. Range: 0 = Inactive 1 = F067 ON 2 = F079 ON 3 = F067 and F079 ON Properties: Description: This parameter allows individually disabling the fault detection by software: a) F067 - Inverted Encoder/Motor Wiring and b) F079 - Encoder Signal Fault.
  • Page 111: Motor

    FAULTS AND ALARMS Table 10.2: Option of parameter P352 P352 Action 0 = OFF Fan off 1 = ON Fan on 2 = CT Fan is controlled via software 10.3.2 Motor The inverter has a function to protect the motor from overtemperature by indicating fault F078. The motor must have a triple PTC type temperature sensor.
  • Page 112 FAULTS AND ALARMS For example, for a constant ratio with 150 % of overload, Fault F072 occurs in 60 seconds. On the other hand, for output current values below P156, P157 or P158 according to the output frequency, fault F0072 does not occur. For ratio values above 150 % the fault actuation time is below 60 s.
  • Page 113 FAULTS AND ALARMS In order to deactivate the motor overload function, just set parameter P156 to P158 to values equal to or above twice the inverter rated current P295. 10-6 | Micro Mini Drives...
  • Page 114: Read

    READ 11 READ It is important to point out that all the parameters of this group can only be viewed on the HMI display, and cannot be changed by the user. P001 - Speed Reference Range: 0 to 9999 Properties: Description: This parameter presents, regardless the origin source, the speed reference value in the unit and scale defined for the reference by P208, P209 and P210.
  • Page 115 READ P006 - Inverter Status Range: 0 = Ready 1 = Run 2 = Undervoltage 3 = Fault 4 = Self-Tuning 5 = Configuration 6 = DC Braking 7 = Reserved 8 = Fire Mode Properties: Description: It indicates one of the possible inverter status. In Figure 11.1 on page 11-3 contains the description of each state, as well as the indication on the HMI.
  • Page 116 READ Description P006 Status Ready Indicates the inverter is ready to be enabled Indicates the inverter is enabled Indicates the voltage in the inverter is too low for operation (undervoltage), and will not accept the enabling command Indicates the inverter is in the fault status. The fault Fault code will flash Indicates the inverter is executing the Self-Tuning...
  • Page 117 ✓ NOTE! The default setting of P397 meets most application needs of the inverter. Therefore, avoid modifying its content without knowing the related consequences. If you are not sure, contact WEG Technical Assistance before changing P397. P038 - Encoder Speed...
  • Page 118 READ P045 - Fan Enabled Time Range: 0 to FFFF (hexa) Properties: Description: It indicates the total number of hours that the heatsink fan remained connected. This value is kept even when the inverter is disconnected. P047 - CONF Status Range: 0 to 33 Properties:...
  • Page 119 READ P680 - Logical Status Range: 0 to FFFF (hexa) Bit 0 = Reserved Bit 1 = Run Command Bit 2 = Fire Mode Bit 3 to 4 = Reserved Bit 5 = 2nd Ramp Bit 6 = Config. Mode Bit 7 = Alarm Bit 8 = Running Bit 9 = Enabled...
  • Page 120 READ P681 - 13-Bit Speed Range: 0 to FFFF (hexa) Properties: Description: The 13-bit Frequency Reference is a scale based on the motor rated speed (P402) or on the motor rated frequency (P403). In the inverter, parameter P403 is taken as the base to determine the frequency reference. Thus, the 13-bit frequency value has a range of 16 bits with signal, that is, -32768 to 32767;...
  • Page 121 READ Table 11.4: Status word P690 Function Description 0 to 2 Reserved 0: Energy saving inactive Energy Saving 1: Energy saving active 0: Output frequency reduction inactive Fs Reduction 1: Output frequency reduction active Reserved 0: No deceleration Deceleration Ramp 1: Inverter accelerating 0: No deceleration Acceleration Ramp...
  • Page 122: Communication

    COMMUNICATION 12 COMMUNICATION In order to exchange information via communication network, the frequency inverter features several standardized communication protocols, such as Modbus (RTU and TCP), CANopen, DeviceNet, Profibus DP and Ethernet IP. For further details referring to the inverter configuration to operate in those protocols, refer to the inverter user’s manual for communication with the desired network.
  • Page 123: Serial

    P685 = 2000h (8192 decimal) → speed reference = rated frequency (P403). For a detailed description, refer to the user manual of the communication network, available for download on the website: www.weg.net. 12.2 SERIAL See below the frequency inverter parameters that are directly related to the Modbus RTU communication.
  • Page 124: Bluetooth

    These parameters are used for configuration and operation of the RS-232, RS-485, USB and Bluetooth. For a description detailed, refer to the Modbus RTU, user’s manual, available for download on the website: www.weg.net. 12.3 BLUETOOTH See below the parameters to configure and operate the Bluetooth interface. For the correct configuration of this interface, it is necessary to configure properly the parameters of the...
  • Page 125: Canopen And Devicenet

    COMMUNICATION ✓ NOTE! Parameter P770 is only available with the bluetooth accessory connected. P771 - Bluetooth Password PIN Range: 0 to 9999 Description: This parameter defines the bluetooth parity password. This password is limited to the four digits available on the inverter display.
  • Page 126 COMMUNICATION P705 - CAN Controller Status Range: 0 = Disabled 1 = Auto-baud 2 = CAN Active 3 = Warning 4 = Error Passive 5 = Bus Off 6 = No Bus Power Properties: P706 - RX CAN Telegrams Range: 0 to 9999 Properties: P707 - TX CAN Telegrams...
  • Page 127 3 = Operational 4 = Preoperational Properties: Description: Parameters for configuration and operation of the CAN interface. For detailed description, refer to manual CANopen communication or DeviceNet communication manual available for download on the website: www.weg.net. 12-6 | Micro Mini Drives...
  • Page 128: Profibus Dp

    COMMUNICATION 12.5 PROFIBUS DP See below the parameters to configure and operate the Profibus interface. P740 - Profibus Comm. Status Range: 0 = Disabled 1 = Access Error 2 = Offline 3 = Config. Error 4 = Param. Error 5 = Clear Mode 6 = Online Properties: P742 - Profibus Read Word #3...
  • Page 129: Ethernet

    Parameters for configuration and operation of the Profibus interface. For a detailed description, refer to the CANopen communication or DeviceNet communication manual available for download on the website: www.weg.net. 12.6 ETHERNET See below the parameters to configure and operate the Ethernet interface.
  • Page 130 COMMUNICATION P858 - Gateway 3 P859 - Gateway 4 Range: 0 to 255 Properties: P860 - MBTCP: Communication Status Range: 0 = Disabled 1 = No connection 2 = Connected 3 = Timeout Error Properties: P863 - MBTCP: Active Connections Range: 0 to 4 Properties:...
  • Page 131 COMMUNICATION P871 - EIP Data Profile Range: 0 = ODVA 20/70: CIP Basic Speed 1 = ODVA 21/71: CIP Enhanced Speed 2 to 3 = Reserved 4 = 20/70: Basic Speed + I/O 5 = 21/71: Enhanced Speed + I/O 6 to 7 = Reserved 8 = 100/150: Speed + I/O 9 to 10 = Reserved...
  • Page 132 Bit 0 = Link 1 Bit 1 = Link 2 Properties: Description: Parameters for configuration and operation of the Ethernet interface. For a detailed description, refer to the manual of Ethernet communication, available for download on: www.weg.net. Micro Mini Drives | 12-11...
  • Page 133: Softplc

    SOFTPLC 13 SOFTPLC The SoftPLC function allows the inverter to assume PLC (Programmable Logical Controller). For further details regarding the programming of those functions in the inverter, refer to the ”Help” menu of the WPS software. 13.1 COMMAND AND STATUS See below the parameters related to the SoftPLC commands and states.
  • Page 134: User

    SOFTPLC Table 13.1: Description of the parameter P903 options P903 Description It defines that the application that will run on the SoftPLC is the one loaded by the user through the ladder programming tool It defines that the application that will run on the SoftPLC is the PID controller WARNING! It is recommended to load the factory setting (P204 = 5 or 6) after alternating between user’s application and PID controller application.
  • Page 135 SOFTPLC P923 - SoftPLC Parameter 14 P924 - SoftPLC Parameter 15 P925 - SoftPLC Parameter 16 P926 - SoftPLC Parameter 17 P927 - SoftPLC Parameter 18 P928 - SoftPLC Parameter 19 P929 - SoftPLC Parameter 20 P930 - SoftPLC Parameter 21 P931 - SoftPLC Parameter 22 P932 - SoftPLC Parameter 23 P933 - SoftPLC Parameter 24...
  • Page 136 SOFTPLC P947 - SoftPLC Parameter 38 P948 - SoftPLC Parameter 39 P949 - SoftPLC Parameter 40 P950 - SoftPLC Parameter 41 P951 - SoftPLC Parameter 42 P952 - SoftPLC Parameter 43 P953 - SoftPLC Parameter 44 P954 - SoftPLC Parameter 45 P955 - SoftPLC Parameter 46 P956 - SoftPLC Parameter 47 P957 - SoftPLC Parameter 48...
  • Page 137: Pid Controller

    APPLICATIONS 14 APPLICATIONS Using the SoftPLC function of the inverter, it is possible to develop an application (or functionality) in ladder language and include it in the inverter software. Parameter P903 allows selecting the application and uploading it to the SoftPLC execution area of the inverter. The frequency inverter has the following application already implanted: PID Controller.
  • Page 138 APPLICATIONS The example below defines the terms used by the PID controller application. An electric pump used in a water pumping system in which the pressure must be controlled at the pump output pipe. A pressure transducer is installed on the pipe and provides an analog feedback signal to the inverter proportional to the water pressure.
  • Page 139: Start-Up

    APPLICATIONS 14.1.1 Start-Up See below the required steps to put the PID controller application into operation. ✓ NOTE! For the PID controller application to work properly, it essential to check if the inverter is configured properly to drive the motor at the desired speed. In order to do so, check the following settings: Acceleration and deceleration ramps (P100 to P101).
  • Page 140 APPLICATIONS Table 14.2: Programming sequence of the PID controller application Indication on the Seq. Action / Result Display It selects the PID controller application in the SoftPLC function of the inverter P903 = 1 It enables the execution of the PID controller application P901 = 1 It selects the PID controller control action, thus enabling its operation and uploading, at this moment P928 = 1...
  • Page 141: Academic Pid Controller

    APPLICATIONS Putting into Operation Check the state of the PID controller application in parameter P900. Value equal to 4 indicates the application is already in operation. Value equal to 3 indicates the application is stopped; therefore, it is necessary to change the command value for the SoftPLC in parameter P901 to 1 (execute application). Value different from 3 or 4 indicates the application cannot go into operation.
  • Page 142 APPLICATIONS P910 - PID Controller Application Version Range: 0.00 to 90.00 Properties: Description: Read-only parameter which presents the software version of the PID controller application developed for the SoftPLC function of frequency inverter. P911 - Control Setpoint Range: -99.99 to 99.99 Description: This parameter defines the setpoint value in automatic mode for the PID controller in engineering unit when the control setpoint source is programmed to be via HMI or communication networks (P920=0).
  • Page 143 APPLICATIONS ✓ NOTE! This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering unit (P510 and P511). The conversion of the value read by the analog input in percentage into the value of the process variable shown in P916 according to the scale is done through the following formula: P916 = [ValorAI(%) x (P923 - P922)] + [P922] P917 - PID Controller Output...
  • Page 144 APPLICATIONS Bits Values Bit 0 0: Inverter is not in the alarm condition Sleep Mode Active (A750) 1: It indicates that the PID controller is in the sleep mode (A750) Bit 1 0: PID controller operating in Manual mode PID Controller in Manual or Automatic 1: PID controller operating in Automatic mode Bit 2 0: Inverter is not in the alarm condition...
  • Page 145 APPLICATIONS Table 14.5: Description of the control setpoint source P920 Description It defines that the control setpoint source in automatic mode of the PID controller will be the value programmed in parameter P911 via HMI of the frequency inverter or written via communication networks It defines that the control setpoint source in automatic mode of the PID controller will be the value read by the analog input AI1.
  • Page 146 APPLICATIONS P921 - Selection of the Control Process Variable Source Range: 1 = Control Process Variable via Analog Input AI1 2 = Control Process Variable via Analog Input AI2 3 = Control Process Variable via Difference between Analog Input AI1 and AI2 Properties: Description: This parameter defines the source of the PID controller process variable.
  • Page 147 APPLICATIONS ✓ NOTE! This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering unit (P510 and P511). P925 - Time for Low Level Fault for the Control Process Variable Range: 0.0 to 999.9 s Description: This parameter defines how long the low level alarm condition should remain so that the control process variable (A760) will generate fault “F761: Low Level Fault of the Control Process Variable”.
  • Page 148 APPLICATIONS This parameter enables the PID controller and defines how the control action will be. Table 14.8: Description of the PID controller control action P928 Description It defines that the PID controller will be disabled It defines that the PID controller will be enabled, and the regulation or control action will be in direct mode. In other words, the error will be the control setpoint value (P911) minus the control process variable value (P916) It defines that the PID controller will be enabled, and the regulation or control action will be in reverse mode.
  • Page 149 APPLICATIONS P930 - Automatic Adjustment of the PID Controller Setpoint Range: 0 = P911 inactive and P918 inactive 1 = P911 active and P918 inactive 2 = P911 inactive and P918 active 3 = P911 active and P918 active Description: This parameter defines if the PID controller setpoint in automatic mode (P911) and/or in manual mode (P918) will be automatically changed or adjusted when the PID controller operation mode changes.
  • Page 150: Sleep Mode

    APPLICATIONS P934 - PID Controller Sampling Period Range: 0.050 to 9.999 s Properties: Description: This parameter defines the sampling time of the PID controller. ✓ NOTE! Table 14.3 on page 14-4 suggests setting values for the sampling time according to the process to be controlled by the PID controller.
  • Page 151 APPLICATIONS P937 - Time to Wake Up Range: 0.0 to 999.9 s Description: This parameter defines the time the wake up mode active condition should remain to start the motor and control the system. The control process variable must remain smaller (direct PID) or greater (reverse PID) than the deviation defined in P936 for the time set in P937 for the motor to be started and its speed controlled.
  • Page 152 APPLICATIONS COMANDS - DIGITAL INPUTS DI1 - run/stop PROCESS VARIABLE P911 - control setpoint P936 - process variable deviation to wake up P937 - time to wake up MOTOR SPEED (Hz) P134 - maximum speed reference P939 - time to activate the sleep mode P938 - motor speed to activate the sleep mode P133 - minimum speed reference...
  • Page 153: Application Examples

    APPLICATION EXAMPLES 15 APPLICATION EXAMPLES This chapter presents some examples of applications of frequency inverters. 15.1 ANALOG INPUTS APPLICATIONS In this section some applications that use analog inputs are shown. Figure 15.1 on page 15-1 present some possible connections. The applications described here require the loading of the factory default (P204 = 5 or 6) for correct execution.
  • Page 154: Appication 1 - Simple Application (Nominal Speed)

    APPLICATION EXAMPLES 15.1.1 Appication 1 - Simple application (nominal speed) This example describes an application where the analogic input signal corresponds as frequency reference. Thus, the total excursion of analogic signal represents the drive of the motor from its minimum frequency to its maximum frequency, as presented on Figure 15.2 on page 15-2.
  • Page 155: Application 2 - Simple Application (Overspeed)

    APPLICATION EXAMPLES 15.1.2 Application 2 - Simple application (overspeed) This example describes an application where the analogic input signal corresponds as frequency reference. Thus, the total excursion of analogic signal represents the drive of the motor from its minimum frequency to its maximum frequency, as presented on Figure 15.3 on page 15-3.
  • Page 156: Application 3 - Analog Input With Reversing

    APPLICATION EXAMPLES 15.1.3 Application 3 - Analog input with reversing In this example, the Analogic Input signal represents as speed reference. The total excursion of analogic signal represents the drive of the motor from its minimum frequency to its maximum frequency, reversing the direction of rotation, as presented on Figure 15.4 on page 15-4.
  • Page 157: Application 4 - Analog Input With Dead Zone

    APPLICATION EXAMPLES 15.1.4 Application 4 - Analog input with dead zone In this example, the output stay in 0Hz through the first 2.5V of analogic signal. The rotation of the motor only happens if the Dead Zone parameter is disable (P230 = 0), as presented on Figure 15.5 on page 15-5.
  • Page 158: Application 5 - Simple Application 2 (Nominal Speed, Inverted Analog Input)

    APPLICATION EXAMPLES 15.1.5 Application 5 - Simple application 2 (nominal speed, inverted analog input) This example describes an application where the analogic input signal corresponds as frequency reference. Thus, the total excursion of analog signal represents the drive of the motor from its minimum frequency to its maximum frequency, as presented on Figure 15.6 on page 15-6.
  • Page 159 WEG Drives & Controls - Automation LTDA. Jaraguá do Sul – SC – Brazil Phone 55 (47) 3276-4000 – Fax 55 (47) 3276-4020 São Paulo – SP – Brazil Phone 55 (11) 5053-2300 – Fax 55 (11) 5052-4212 automacao@weg.net www.weg.net...

This manual is also suitable for:

Cfw300

Table of Contents