Fault / Alarm
A046
Motor overload alarm.
Motor Overload
A050
Overtemperature alarm from the power
Power Module
module temperature sensor (NTC).
Overtemperature
A090
External alarm via DIx (option "No
External Alarm
External Alarm" in P26x).
A128
Alarm that indicates serial communication
Telegram Reception
fault. It indicates the equipment stopped
Timeout
receiving valid serial telegrams for a period
longer than the setting in P314.
A133
It indicates that the CAN interface has no
No power supply on the
power supply between pins 1 and 5 of
CAN interface
the connector.
A134
Buss off error detected on the CAN
Bus Off
interface.
A135
CANopen communication error control
Node Guarding/
detected communication error using the
Heartbeat
guarding mechanism.
A136
Alarm indicates that the DeviceNet
Idle Master
network master is in Idle mode.
A137
Alarm that indicates that one or more
DeviceNet Connection
DeviceNet connections timed out.
Timeout
A163
Analog input signal AI1 at 4 to 20 mA or
Signal Fault AI1
20 to 4 mA is below 4-20 mA.
A700
No communication with remote HMI, but
Remote HMI
here is frequency command or reference
Communication Fault
for this source.
A702
This failure occurs when there is a
Inverter Disabled
SoftPLC movement block (REF block)
active and the "General Enable"
command is disabled.
A704
It occurs when 2 or more SoftPLC
Two Movem. Enabled
movement blocks (REF Block) are
enabled at the same time.
A706
This failure occurs when a SoftPLC
Refer. Not Prog. SPLC
movement block is enabled and the
speed reference is not programmed for
the SoftPLC.
A712
It occurs when there is an attempt to
SPLC protected against
copy the SoftPLC application protected
copy
against copies.
Quick Reference of Parameters, Alarms and Faults
Description
Return
Advance
Possible Causes
Settings of P156 is too low for the used motor.
Overload on the motor shaft.
High temperature at IGBTs (P030 > 110 °C).
High ambient temperature around the inverter (>50 °C (> 122 °F))
and high output current.
Blocked or defective fan.
Heatsink is too dirty, preventing the air flow.
Wiring on DI1 to DI4 inputs are open or have poor contact.
Check network installation, broken cable or fault/poor contact
on the connections with the network, grounding.
Ensure the master always sends telegrams to the equipment
in a time shorter than the setting in P314.
Disable this function in P314.
Measure if there is voltage within the allowed range between
pins 1 and 5 of the CAN interface connector.
Check if the power supply cables are not misconnected or
inverted.
Check for contact problems on the cable or connector of the
CAN interface.
Check for short circuit on the CAN circuit transmission cable.
Check if the cables are not misconnected or inverted.
Check if all the network devices use the same baud rate.
Check if the termination resistors with the right specification
were installed only at the end of the main bus.
Check if the CAN network was properly installed.
Check the times set on the master and on the slave for message
exchange. In order to prevent problems due to transmission
delays and time counting, it is recommended that the values
set for error detection by the slave be multiples of the times set
for message exchange on the master.
Check if the master is sending the guarding telegrams in the
time set.
Check problems in the communication that may cause missing
telegrams or transmission delays.
Set the switch that controls the master operation of the master
for Run or the corresponding bit on the configuration word of
the master software. If further information is needed, refer to
the documentation of the master used.
Check the network master status.
Check network installation, broken cable or fault/poor contact
on the connections with the network.
Cable of AI1 broken.
Poor contact at the signal connection on the terminals.
Check if the communication interface with the HMI is properly
configured in parameter P312.
HMI cable disconnected.
Check if the drive General Enable command is active.
Check the user's program logic.
Check the programming of the references in the Local and/or
Remote mode (P221 and P222).
Attempt to copy WLP application protected against copies
("never permit copies").
Attempt to copy WLP from a copy protected against copies
("no permission to copy from a copy")