10.1 VVW VECTOR CONTROL PARAMETERIZATION

The V V W control mode is selected by parameter P202, control mode selection, as described in
AVAILABLE MOTOR CONTROL TYPES on page
Opposite to the V/f scalar control, the V V W control requires a series of data from the motor nameplate and a
self-tuning for its proper operation. Besides, it is recommended that the driven motor match the inverter, that is,
the motor and inverter power be as close as possible.
Below are described the parameters to configure the V V W vector control setting. This data is easily obtained on
WEG standard motor nameplates, however in older motors or motors made by other manufacturers, the data
may not be readily available. In those cases, it is recommended first contact the motor manufacturer, measure or
calculate the desired parameter. As a last resort, the user always can make a relationship with
10-3
and use the equivalent or approximate WEG standard motor parameter.
NOTE!
The correct setting of the parameters directly contributes to the V V W control performance.
Power [P404]
Frame
size
(CV)
(kW)
0.16
0.12
63
0.25
0.18
63
0.33
0.25
63
0.50
0.37
71
0.75
0.55
71
1
0.75
80
0.16
0.12
63
0.25
0.18
63
0.33
0.25
71
0.50
0.37
71
0.75
0.55
80
1
0.75
80
P178 – Rated Flux
Adjustable
50.0 to 150.0 %
Range:
Properties:
V V W
Description:
It defines the desired flux in the motor air gap in percentage (%) of the rated flux. In general, it is not necessary
to modify the value of P178 of the standard value of 100 %. However, some specific situations may use values
slightly above to increase the torque, or below to reduce the energy consumption.
P399 – Motor Rated Efficiency
Adjustable
50.0 to 99.9 %
Range:
Properties:
cfg, V V W
Description:
This parameter is important for the precise operation of the V V W control. A misconfiguration will cause incorrect
calculation of the slip compensation, reducing the performance of the speed control.
8-1.
Table 10.1: Characteristics of IV pole WEG standard motors
Voltage
Current
Frequency
[P400]
[P401]
[P403]
(V)
(A)
(Hz)
0.85
1.12
1.42
220
60
2.07
2.90
3.08
0.73
1.05
1.40
230
50
1.97
2.48
3.23
Return
Advance
V V W Vector Control
Speed
Efficiency
Power
[P402]
[P399]
Factor
(rpm)
(%)
[P407]
1720
56
0.66
1720
64
0.66
1720
67
0.69
1720
68
0.69
1720
71
0.70
1720
78
0.82
1375
57
0.72
1360
58
0.74
1310
59
0.76
1320
62
0.76
1410
68
0.82
1395
72
0.81
Factory
Setting:
Factory
Setting:
chapter 8
Table 10.1 on page
Stator Resistance
[P409]
(Ω)
21.77
14.87
10.63
7.37
3.97
4.13
30.62
20.31
14.32
7.27
5.78
4.28
10
100.0 %
67.0 %
CFW100 | 10-3