Mitsubishi Electric MELSEC-L Series LD40PD01 User Manual page 82

Flexible high-speed i/o control module
Table of Contents

Advertisement

Block setting
Configure block settings by changing values in the drop-down lists and text boxes of each block.
(1)
(2)
No.
Item name
(1)
Drop-down list
(2)
Text box
(3)
User Address
■Input range of User Address
Input range
Description
1000 to 1029
• The monitor items and setting items assigned in this area are read or written at a high speed (100μs). These items are also read or
written when the flexible high-speed I/O control module sends an interrupt signal to the CPU module.
• Assign even addresses to the parameters of two words (32 bits). Odd addresses cannot be assigned.
1030 to 1099
• The monitor items and setting items assigned in this area are read or written at a low speed (1ms).
• Assign even addresses to the parameters of two words (32 bits). Odd addresses cannot be assigned.
A single buffer memory address cannot be specified in several "User Address".
For example, when the buffer memory address 1000 has been specified in "Count Value" and 1000 is
specified in "Latch Value", the value in User Address is returned to the initial value.
8 FUNCTIONS OF THE CONFIGURATION TOOL
80
8.7 Windows for Creating the Hardware Logic
Description
Select a setting value from the drop-down list.
Input a one-byte numerical value (decimal).
• By assigning buffer memory addresses to "User Address", input terminal status and parameter setting
values can be changed with programs and values of a hardware logic can be monitored during the
hardware logic control. For details, refer to the following ( Page 133 Assignment of "User Address").
• Input decimal values in the setting.
• The range of settable buffer memory addresses is 1000 to 1099 (High speed area: 1000 to 1029, low
speed area: 1030 to 1099). For details, refer to the following ( Page 80 Input range of User Address).
(3)