Mitsubishi Electric MELSEC-L Series LD40PD01 User Manual page 140

Flexible high-speed i/o control module
Table of Contents

Advertisement

Variable name
B: Fall
B: Low
B: High
A: Rise+B: Low
A: Rise+B: High
A: Fall+B: Low
A: Fall+B: High
9 CREATING A HARDWARE LOGIC
138
9.2 Multi Function Counter Block
Data type
Valid range
Bit
OFF
ON
Bit
OFF
ON
Bit
OFF
ON
Bit
OFF
ON
Bit
OFF
ON
Bit
OFF
ON
Bit
OFF
ON
Default value
Description
OFF
When the fall of "Input B" has been detected, Output
turns to High only for one clock cycle. The status of
"Input A" does not affect the status of Output.
Input A
Input B
Output
OFF
While "Input B" is Low, Output is High. The status of
"Input A" does not affect the status of Output.
Input A
Input B
Output
OFF
While "Input B" is High, Output is High. The status of
"Input A" does not affect the status of Output.
Input A
Input B
Output
OFF
When the rise of "Input A" and the Low state of "Input
B" have been detected, Output turns to High only for
one clock cycle.
Input A
Input B
Output
OFF
When the rise of "Input A" and the High state of "Input
B" have been detected, Output turns to High only for
one clock cycle.
Input A
Input B
Output
OFF
When the fall of "Input A" and the Low state of "Input B"
have been detected, Output turns to High only for one
clock cycle.
Input A
Input B
Output
OFF
When the fall of "Input A" and the High state of "Input
B" have been detected, Output turns to High only for
one clock cycle.
Input A
Input B
Output