Commissioning (block-based operation)
114
12.8.2
Factory settings of the on-site display for interface
measurements
Parameter
Factory setting for devices with 1 current
output
Format display 1 value, max. size
Value 1 display Interface
Value 2 display Level linearized
Value 3 display Upper interface thickness
Value 4 display Current output 1
The on-site display can be adjusted in the DISPLAY (TRDDISP) transducer block.
12.9

Configuration management

After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration. You can do so using the
Configuration management parameter and its options.
Navigation path in the operating menu
Setup → Advanced setup → Conf.backup disp → Config. managem.
Block operation
Block: DISPLAY (TRDDISP)
Parameter: Configuration management (configuration_management)
Functions of the parameter options
Options
Description
33097: Execute backup
A backup copy of the current device configuration in the HistoROM is saved to the
display module of the device. The backup copy comprises the transmitter data of
the device.
33057: Restore
The last backup copy of the device configuration is copied from the display module
to the HistoROM of the device. The backup copy comprises the transmitter data of
the device.
33838: Duplicate
The transmitter configuration from another device is duplicated to the device using
the display module.
265: Compare
The device configuration saved in the display module is compared to the current
device configuration of the HistoROM.
32848: Clear backup data
The backup copy of the device configuration is deleted from the display module of
the device.
HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.
While this action is in progress, the configuration cannot be edited via the local
display and a message on the processing status appears on the display.
For devices with FOUNDATION Fieldbus communication, the PD Tag parameter is
also transmitted when duplicating the parameter configuration. If required change PD
Tag to the required value after duplicating the set.
Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
Factory setting for devices with 2 current
outputs
1 value, max. size
Interface
Level linearized
Current output 1
Current output 2