Operating menu
Level correction
Navigation
Description
User entry
Factory setting
Additional information
Manual thickness upper layer
Navigation
Description
User entry
Factory setting
184
1
Suppression of interference echoes at the top end of the probe.
2
Suppression of the level signal in case of a flooded bypass.
UB Upper blocking distance
 Setup → Advanced setup → Interface → Level correction
Specify level correction (if required).
–200 000.0 to 200 000.0 %
0.0 %
The value specified in this parameter is added to the measured total and interface levels
(before linearization).
Setup → Advanced setup → Interface → Man.thick.up.lay
Specify the manually determined interface thickness UP (i.e. the thickness of the upper
medium).
0 to 200 m
0 m
Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
1
UB
2
UB
Endress+Hauser
A0013220