Commissioning (block-based operation)
108
XD_SCALE
EU_100
EU_0
0
25
Scaling of the measured value in an AI Block
• If you have selected the Direct mode for the L_TYPE parameter, you cannot change
the values and units for XD_SCALE and OUT_SCALE.
• The L_TYPE, XD_SCALE and OUT_SCALE parameters can only be changed in the
OOS block mode.
12.4
Language selection
Step
Block
1
DISPLAY (TRDDISP)
1)
When ordering a device the set of available languages is defined. Refer to the product structure, feature
500 "Additional Operation Language".
12.5
Checking the reference distance
This section is only valid for FMP54 with gas phase compensation (product structure:
feature 540 "Application Package", option EF or EG).
Coax probes with gas phase compensation are calibrated on delivery. Rod probes, on the
other hand, must be recalibrated after mounting:
After mounting the rod probe in the stilling well or bypass, check and - if necessary -
correct the setting of the reference distance in the unpressurized state. Whilst doing so the
Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
1
0
EU_0
1
Parameter
Language (language)
OUT_SCALE
EU_100
OUT_VALUE
Action
1)
Select language
.
Selection:
• 32805: Arabian
• 32824: Chinese simplified
• 32842: Czech
• 32881: Dutch
• 32888: English
• 32917: French
• 32920: German
• 32945: Italian
• 32946: Japanese
• 32948: Korean
• 33026: Polish
• 33027: Portuguese
• 33062: Russian
• 33083: Spanish
• 33103: Thai
• 33120: Vietnamese
• 33155: Bahasa
• 33166: Turkish
Endress+Hauser
A0017338